Step 2. Install Jumpers
Master Reset and Upgrade Jumpers
Jumpers labeled MRST and UPGD are the Master Reset and Upgrade jumpers, respectively.
JP1 on the main board contains two jumpers, MRST and UPGRD. The MRST jumper is the Master Reset jumper.
When MRST is connected, the controller will perform a master reset upon PC power up or upon the reset input
going low. The MRST can also be set with the DIP switches on the outside of the controller. Whenever the
controller has a master reset, all programs, arrays, variables, and motion control parameters stored in EEPROMwill
be ERASED.
The UPGD jumper enables the user to unconditionally update the controller’s firmware. This jumper should not be
used without first consulting Galil.
Step 3. Configure Dip Switches
Located on the outside of the controller box is a set of 8 DIP switches. Whent eh controller is powered on or reset,
the state of the DIP switches are read.
Switch 1 – Master Reset
When this switch is on, the controller will perform a master reset upon PC power up. Whenever the controller has
a master reset, all programs and motion control parameters stored in EEPROM will be ERASED. During normal
operation, this switch should be off.
Switches 2,3, and 4 are non-functional and reserved
Switches 5 and 6 Main Serial Port Baud Rate
If using the RS232 port for communication, the baud rate is set via switches 5 and 6. To set the baud rate, configure
switches 5 and 6as follows:
Switch 5 -19.2
Switch 6 – 38.4
BAUD RATE
ON
OFF
19200
OFF
ON
38400
ON
ON
115200
Switch 7 – Option
When OFF, the controller will use the auto-negotiate function to set the Ethernet connection speed. When the DIP
switch is ON, the controller defaults to 10BaseT.
Switch 8 – Motor Off
It is recommended to use the MO switch when connecting motors for the first time. With the MO switch ON, the
controller will boot-up in the “motor off” state. In this state the amplifier enable signals are toggled to
“inhibit/disable”. With this switch OFF
Chapter 2 Getting Started ▫ 12
DMC-42x0 User Manual
Содержание DMC-42 0 Series
Страница 85: ...Chapter 6 Programming Motion 81 DMC 42x0 User Manual Figure 6 14 ECAM cycle with Z axis as master...
Страница 195: ...ICM 2900 PCB Layout Appendices 191 DMC 42x0 User Manual...
Страница 205: ...CB 50 100 Drawings Appendices 201 DMC 42x0 User Manual...
Страница 206: ...Appendices 202 DMC 42x0 User Manual...
Страница 207: ...Appendices 203 DMC 42x0 User Manual...
Страница 208: ...Appendices 204 DMC 42x0 User Manual...
Страница 209: ...Appendices 205 DMC 42x0 User Manual...
Страница 210: ...Appendices 206 DMC 42x0 User Manual...
Страница 211: ...Appendices 207 DMC 42x0 User Manual...
Страница 214: ...CB 50 80 Drawing Appendices 210 DMC 42x0 User Manual...
Страница 215: ...Appendices 211 DMC 42x0 User Manual...