ADvANCED ADjUSTMENTS

 lOAD SHARiNG ADjUStMENt

 lOAD ANtiCiPAtiON ADjUStMENt

 REvERSE POWER ADjUStMENt

When proper phasing has been confirmed, the generators can be synchronized and paralleled. With the system paralleled and oper

-

ating with no load, adjust each governor’s speed trim for zero real power as indicated on each generator set’s hertz-meter. 

The system should be stable and no significant power from either generator should be indicated. If the system does not seem stable, 

adjust each of the LOAD SENSITIVITY controls CCW about 1/3 of a turn or until the system is stable. If the sensitivity is set below 40 

%, refer to System Troubleshooting section. 

Electrical load can now be applied to the system. 

All generator sets in the system should be sharing the systems load nearly proportionally. The generator set carrying the least 

amount of load should be adjusted to accept more of the total system load. Turn the LOAD SENSITIVITY control adjustment CCW 

on this unit to increase its load contribution.

The LOAD ANTICIPATION adjustment is factory set to zero sensitivity. To improve the genset’s transient response, gradually 

advance the adjustment CW to about 50 % while the generator sets are in parallel. The transient response improvement can be ob-

served when the engine load is changed. An optimum setting requires a speed recorder to minimize the transient in both magnitude 

and duration. Instability may result it the adjustment is advanced too far CW.

With the reset switch or jumper across Terminals 18 and 19, the reverse power monitor can be calibrated. To obtain reverse power 

on a generator may be difficult. An alternate method is to simulate reverse power by reversing all the CTs temporarily when the unit 

is in single unit operation.

NOTE: No serviceable points, parts or adjustments internally.

With the CTs still reversed, adjust the monitor’s setting from 20 to 100 and the DELAY to fastest (full CCW). Apply a small amount of 

load representing the trip point of the reverse power monitor, approximately 10 %. Turn the REVERSE POWER MONITOR adjustment 

from 100 slowly toward 0 until the monitor turns on. Remove the generator load. The monitor should turn OFF (reset). Recheck the 

setting by applying the 10% load again.

The Reverse Power Delay may now be set by turning this adjustment CW. The minimum delay necessary should be used, otherwise 

leave this setting to full CCW (minimum delay).

NOtE

The delays are of the inverse time type. See previous description for details. Be sure to reinstate the CT connections 

to their proper polarity before attempting parallel operation.

The analog power output voltage signal is a good measure of engine power when the AC voltage from the generator is considered 

to be constant. The external power meter can be any analog or digital meter with a relatively high input impedance (>10 K Ω) that is 

within the voltage range of the unit. The (+) signal output is at Terminal 32 and the reference is at Terminal 33(-). Terminal 33 is refer-

enced at a voltage of 2.0 V DC above battery minus. Limit Terminal 32 to 10 ma.

 

The maximum range of voltage is -2 to +5 V DC across these two terminals. The bipolar output allows reverse power as well as 

forward power to be detected. The EXTERNAL POWER METER CAL adjustment (-1 to % V DC) allows this signal to be adjusted for 

lower levels to match the external instruments. CCW adjustment reduces the voltage range.  Proportional to the CT current an output 

of 5V indicates 5 A CT power (forward), and -1V indicates 1 A (reverse).

The internal bar graph is taken from the same voltage source. The bar graph can be calibrated for generator power output. The third 

dot is zero power output and the 10th dot is 100% output. After full power has been applied to the generator, adjust the GENERATOR 

POWER DISPLAY CAL for a full scale reading. Be sure the adjustment is made by turning the adjustment CW from the zero position.

 POWER MEtER OPERAtiON

When in parallel with the mains under power control, if the mains fail the LSM200 Series load sharing module must revert to isochro-

nous load sharing quickly. The connection across the parallel cable (Terminals 10 and 11) must be opened and the mains load sharing 

reduced to zero quickly (Terminals 15 to 16 connection). Defeating the mains ramp using a connection from Terminal 20 to 21. See 

Section 5 Wiring diagram.

If the generator power control function is not used, adjust the RAMP and ADJUST to their 0 settings.

 POWER RAMP DEFEAt - OPtiONAl

Содержание LSM200 Series

Страница 1: ...nest electric governors have minor frequency differences among units to be paralleled which would cause power variations In this case one generator set would continuously increase the power it produces while the other sets would decrease the power they produce This condition eventually leads to motorizing one or more generator engines The load sharing system continuously adjusts the governor speed...

Страница 2: ...nerator sets that are to be synchronized must be tested independently for their maximum capabilities Information should be gath ered for reference if operational issues arise after installation of this product Read this entire installation manual before starting installation of this product An overspeed shutdown device independent of the governor system should be used to prevent loss of engine con...

Страница 3: ...erator Electrical connections are illustrated in the wiring diagrams Choice of a proper wire size is dependent on the maximum current expected at specific terminals of the load sharing module Large gauge wire should be used for Current Transformer CT Terminals 4 to 9 as the current can reach a maximum of 5 A Long wires with high resistance can add to the burden of the CT shielded wire is recommend...

Страница 4: ...4 Governors America Corp 2021 Copyright All Rights Reserved LSM200 Series Load Sharing Modules 6 2021 B1 PIB4100 LSM201N STANDARD FILTERING 4 WIRING ...

Страница 5: ...s common mode signals Battery minus for all generators must be connected together to limit high common mode signals indicating an unbalanced load condition Each load sharing unit takes action to control its governor to minimize this imbalance The imbalance should be less than 2 when the system is adjusted properly The parallel cable voltage is proportional to the load on the generator The voltage ...

Страница 6: ...osition 100 the delay is about 30 s An internal relay with 10 A Form C contacts normally open NO and normally closed NC are included at Ter minals 28 29 and 30 along with an LED to signal the monitor relay status 1 Always set the ON point first with the delay set to minimum delay With the ON adjustment at a setting of 80 adjust the generator load for a desired trip point i e 90 load Turn the ON ad...

Страница 7: ... are possible if the capability of the engine is not limiting the system Optimize this adjustment with repetitive load steps ILC Individual Load Control and Load Ramping Load Anticipation Function Solder a jumper wire across these posts without damaging the circuit board When a reverse power condition occurs the internal relay will activate and latch To reset the relay open the external Reverse Po...

Страница 8: ...ay Full CCW Fastest Load Sensitivity 100 Most Sensitive Load Anticipation 0 0 External Power Meter Cal 100 Max Range ILC Load Ramp 20 Approx 4 Sec Generator Power Ramp 0 0 Generator Power Adjust 0 0 Generator Power Display Cal 50 5 Amps Full Scale Terminal Voltage Measurement Value 31 to 23 Internal Power Supply 10 6 0 2 V DC 12 to 23 Output to Governor 5 0 0 1 V DC Terminal Voltage Measurement Va...

Страница 9: ...ent from 100 slowly toward 0 until the monitor turns on Remove the generator load The monitor should turn OFF reset Recheck the setting by applying the 10 load again The Reverse Power Delay may now be set by turning this adjustment CW The minimum delay necessary should be used otherwise leave this setting to full CCW minimum delay Note The delays are of the inverse time type See previous descripti...

Страница 10: ... above readings look for an open generator neutral connection missing AC current or AC voltage signal or SW1 voltage range switch set improperly 10 To confirm that the Load Sharing portion is controlling the governor temporarily connect a jumper across Terminals 10 to 11 and short Terminals 13 to 14 11 Apply load to the engine The speed of the engine should fall droop as more load is applied to th...

Страница 11: ...ded to use shielded cable for all external connections Be sure that only one end of the shields including the speed sensor shield is connected to a single point on the case of the speed control unit Mount the speed control to a grounded metal back plate or place it in a sealed metal box Radiation is when the interfering signal is radiated directly through space to the governing system To isolate t...

Отзывы: