LSM200 Series Load Sharing Modules  6-2021-B1   PIB4100 

The governor system can be adversely affected by large interfering signals that are conducted through the cabling or through direct 

radiation into the control circuits.

All GAC speed control sensors contain filters and shielding designed to protect the units sensitive circuits from moderate external 

interfering sources.

Although it is difficult to predict levels of interference, applications that include magnetos, solid sate ignition systems, radio transmit

-

ters, voltage regulators or battery chargers should be considered suspect as possible interfering sources.

If it is suspected that external fields, either those that are radiated or conducted, are or will affect the governor systems operation, 

it is recommended to use shielded cable for all external connections.  Be sure that only one end of the shields, including the speed 

sensor shield, is connected to a single point on the case of the speed control unit.  Mount the speed control to a grounded metal 

back plate or place it in a sealed metal box.

• 

Radiation is when the interfering signal is radiated directly through space to the governing system.  To isolate the governor sys-

tem electronics from this type of interference source, a metal shield or a solid metal container is usually effective.

• 

Conduction is when the interfering signal is conducted through the interconnecting wiring to the governor system electronics.  

Shielded cables and installing filters are common remedies.

In severe high-energy interference locations such as when the governor system is directly in the field of a powerful transmitting 

source,  the shielding may require to be a special EMI class shielding.  For these conditions, contact GAC for specific recommenda

-

tions.

8

TROUBLEShOOTING (CONTINUED)

 

EMi SUSCEPtiBilitY

Содержание LSM200 Series

Страница 1: ...nest electric governors have minor frequency differences among units to be paralleled which would cause power variations In this case one generator set would continuously increase the power it produces while the other sets would decrease the power they produce This condition eventually leads to motorizing one or more generator engines The load sharing system continuously adjusts the governor speed...

Страница 2: ...nerator sets that are to be synchronized must be tested independently for their maximum capabilities Information should be gath ered for reference if operational issues arise after installation of this product Read this entire installation manual before starting installation of this product An overspeed shutdown device independent of the governor system should be used to prevent loss of engine con...

Страница 3: ...erator Electrical connections are illustrated in the wiring diagrams Choice of a proper wire size is dependent on the maximum current expected at specific terminals of the load sharing module Large gauge wire should be used for Current Transformer CT Terminals 4 to 9 as the current can reach a maximum of 5 A Long wires with high resistance can add to the burden of the CT shielded wire is recommend...

Страница 4: ...4 Governors America Corp 2021 Copyright All Rights Reserved LSM200 Series Load Sharing Modules 6 2021 B1 PIB4100 LSM201N STANDARD FILTERING 4 WIRING ...

Страница 5: ...s common mode signals Battery minus for all generators must be connected together to limit high common mode signals indicating an unbalanced load condition Each load sharing unit takes action to control its governor to minimize this imbalance The imbalance should be less than 2 when the system is adjusted properly The parallel cable voltage is proportional to the load on the generator The voltage ...

Страница 6: ...osition 100 the delay is about 30 s An internal relay with 10 A Form C contacts normally open NO and normally closed NC are included at Ter minals 28 29 and 30 along with an LED to signal the monitor relay status 1 Always set the ON point first with the delay set to minimum delay With the ON adjustment at a setting of 80 adjust the generator load for a desired trip point i e 90 load Turn the ON ad...

Страница 7: ... are possible if the capability of the engine is not limiting the system Optimize this adjustment with repetitive load steps ILC Individual Load Control and Load Ramping Load Anticipation Function Solder a jumper wire across these posts without damaging the circuit board When a reverse power condition occurs the internal relay will activate and latch To reset the relay open the external Reverse Po...

Страница 8: ...ay Full CCW Fastest Load Sensitivity 100 Most Sensitive Load Anticipation 0 0 External Power Meter Cal 100 Max Range ILC Load Ramp 20 Approx 4 Sec Generator Power Ramp 0 0 Generator Power Adjust 0 0 Generator Power Display Cal 50 5 Amps Full Scale Terminal Voltage Measurement Value 31 to 23 Internal Power Supply 10 6 0 2 V DC 12 to 23 Output to Governor 5 0 0 1 V DC Terminal Voltage Measurement Va...

Страница 9: ...ent from 100 slowly toward 0 until the monitor turns on Remove the generator load The monitor should turn OFF reset Recheck the setting by applying the 10 load again The Reverse Power Delay may now be set by turning this adjustment CW The minimum delay necessary should be used otherwise leave this setting to full CCW minimum delay Note The delays are of the inverse time type See previous descripti...

Страница 10: ... above readings look for an open generator neutral connection missing AC current or AC voltage signal or SW1 voltage range switch set improperly 10 To confirm that the Load Sharing portion is controlling the governor temporarily connect a jumper across Terminals 10 to 11 and short Terminals 13 to 14 11 Apply load to the engine The speed of the engine should fall droop as more load is applied to th...

Страница 11: ...ded to use shielded cable for all external connections Be sure that only one end of the shields including the speed sensor shield is connected to a single point on the case of the speed control unit Mount the speed control to a grounded metal back plate or place it in a sealed metal box Radiation is when the interfering signal is radiated directly through space to the governing system To isolate t...