GAC ESD5100 Series Скачать руководство пользователя страница 1

E

NGINE

G

OVERNING

S

YSTEM

ESD5100 Series 

Speed Control Unit

Governors America Corp.,  720 Silver Street  Agawam, MA  01001

phone:  413.786.5600    fax:  413.789.7736

www.governors-america.com

[email protected]

1

OVERNORS

MERICA

ORP.

C

A

G

®

ISO 9001

CERTIFIED

INSTAllATION

The ESD5100 Series speed control unit is rugged enough 

to be placed in a control cabinet or engine mounted enclo-

sure with other dedicated control equipment.  If water, mist, 

or condensation may come in contact with the controller, it 

should be mounted vertically.  This will allow the fluid to drain 

away from the speed control unit. Extreme heat should be 

avoided.

WIRING

 

Basic electrical connections are illustrated in Diagram 2.  Ac-

tuator and battery connections to Terminals A, B, E, and F 

should be #16 AWG (1.3 mm sq.) or larger.  Long cables 

require an increased wire size to minimize voltage drops.

The battery positive (+) input, Terminal F, should be fused for 

15 amps as illustrated.  The ESD5100 series is suitable for 

12 VDC and 24 VDC operation.

Magnetic speed sensor wires connected to Terminals C and 

D MUST BE TWISTED AND/OR SHIELDED for their entire 

length.  The speed sensor cable shield should ideally be 

connected as shown in Diagram 2.  The shield should be 

insulated to insure no other part of the shield comes in con-

tact with engine ground, otherwise stray speed signals may 

be introduced into the speed control unit.  With the engine 

stopped, adjust the gap between the magnetic speed sensor 

and the ring gear teeth.  The gap should not be any smaller 

than 0.020 in. (0.45 mm).  Usually, backing out the speed 

sensor 3/4 turn after touching the ring gear teeth will achieve 

a satisfactory air gap.  The magnetic speed sensor voltage 

should be at least 1 VAC RMS during cranking.

ADjUSTMENTS

 

Before Starting Engine

Check to insure the GAIN and STABILITY adjustments, and 

if applied, the external SPEED TRIM CONTROL are set to 

mid position.

Start Engine

The speed control unit governed speed setting is factory set 

at approximately engine idle speed.  (1000 Hz., speed sen-

sor signal)

Crank the engine with DC power applied to the governor sys-

tem.  The actuator will energize to the maximum fuel position 

until the engine starts.  The governor system should control 

the engine at a low idle speed.  If the engine is unstable after 

starting, turn the GAIN and STABILITY adjustments counter-

clockwise until the engine is stable.

Governor Speed Setting

The governed speed set point is increased by clockwise ro-

tation of the SPEED adjustment pot.  Remote speed adjust-

ment can be obtained with an optional 5K Speed Trim Con-

trol.  (See Diagram 2)

Governor Performance

Once the engine is at operating speed and at no load, the 

following governor performance adjustment can be made.

A.  Rotate the GAIN adjustment clockwise until instability 

develops.  Gradually move the adjustment counterclock-

wise until stability returns.  Move the adjustment one 

division further counterclockwise to insure stable perfor-

mance (270° pot).

B.  Rotate the STABILITY adjustment clockwise until insta-

bility develops.  Gradually move the adjustment coun-

terclockwise until stability returns.  Move the adjustment 

one division further to insure stable performance (270° 

pot).

C.  Gain and stability adjustments may require minor chang-

es after engine load is applied.  Normally, adjustments 

made at no load achieve satisfactory performance.  A 

strip chart recorder can be used to further optimize the 

adjustments.

If instability cannot be corrected or further performance im-

provements are required, refer to the SYSTEM TROUBLE-

SHOOTING section.  In this section, information can be found 

regarding troubleshooting procedures as well as instructions 

on adjusting the DIP switch positions of the ESD5131.

Idle Speed Setting

After the governor speed setting had been adjusted, place 

the optional external selector switch in the IDLE position.  

The idle speed set point is increased by clockwise of the 

IDLE adjustment control.  When the engine is at idle speed, 

the speed control unit applies droop to the governor System 

to insure stable operation.

WARNING

An overspeed shut down device, indepen-

dent of the governor system, should be 

provided to prevent loss of engine control, 

which may cause personal injury or equip-

ment damage. Do not rely exclusively on the 

governor system electric actuator to prevent 

overspeed. A secondary shut off device, 

such as a fuel solenoid, must be used.

Отзывы: