4.16 Smart IO Communication Utility
The default communication parameters of the monitor module (new module or one that has factory reset
applied) do not match the proper settings required to communicate with the MCTB. The Smart IO
Communication Utility (accessed from the File menu) provides quick, easy method to configure the monitor
module parameters via the touch of a button.
In order to use the utility, the monitor module must be connected to the RS485 master interface of the MCTB
and have its communication address properly set via the two rotary dials (see section
Press the “Detect Monitor Point Card” button and the utility will attempt to set the
communication parameters. On success, a prompt will be shown to cycle power to the monitor module. Once
power is cycled, the MCTB will then be able to communicate with the monitor module and the inputs can be
configured.
If the utility is unable to set the monitor module communication parameters, verify that the communication wiring
is properly connected and the address is properly set (both rotary dials to one). If the monitor module has been
previously used in another application, it may be possible that the default communication parameters are not
in use. To reset the monitor module to default values, press and hold the initialization button for approximately
3 seconds. The three LED indicators at the top of the module will blink once the reset has been performed.
Cycle power to the monitor module after the reset is performed and again press the “Detect Monitor Point Card”
button on the MCTB. The MCTB should then be able to set the proper communication settings. Upon success,
be sure to cycle power to the monitor module so that it will begin using the new communication settings.
NOTE:
When the initialization is performed, all input type selections will be returned to the factory default of
+10VDC. Input types will have to be reconfigured any time a factory reset is performed.
Содержание MCTB 4.3
Страница 24: ...MCTB 24...
Страница 195: ...MCTB 195...
Страница 227: ...MCTB 227 A 5 SmartIO Monitor Module Specifications...
Страница 228: ...MCTB 228 A 6 Expansion IO Module Specifications...
Страница 229: ...MCTB 229 A 7 Power Supply Specifications DIN Rail Mount Power Supply Specifications...
Страница 230: ...MCTB 230...
Страница 231: ...MCTB 231 Open Frame Power Supply Specifications...
Страница 232: ...MCTB 232...
Страница 233: ...MCTB 233 A 8 Power On Delay Relay Specifications GE1A C10HA110...
Страница 234: ...MCTB 234...