36-G  1/01

Water Gauge & Gauge Glass

Installation instructions

NOTE

Only properly trained personnel

should install and maintain water

gauge glass and connections.

Wear safety glasses during

installation.  Before installing,

make sure all parts are free of

chips and debris.

NOTE

Keep gauge glass in original pack-

aging until ready to install.
1)  

Verify the proper gauge has been

supplied.

2) 

Examine the gauge glass and

packings carefully for damage before

installation.  Do not use the glass if it

contains any scratches, chips, or any

other visible signs of damage.

3)  

Do not subject the gauge glass to

bending or torsional stresses.

4)

Apply teflon tape or pipe dope to

pipe threads.  Install top gauge fitting

(fitting without a drain valve) into the

uppermost tapping.  Wrench tighten

the fitting until it is snug and the glass

outlet is pointing at five o’clock (about

1/8 turn from its final downward verti-

cal position).

5) 

Install the bottom gauge fitting

(the fitting with a drain valve) until it is

snug and the glass outlet is pointing

directly upward.  Verify top and bot-

tom fittings are threaded into the tap-

pings the same number of turns (dis-

tance A=distance B).

6)

Remove glass packing nut, friction

washer and glass packing from the

fittings, and place them, in the same

order, on to both ends of the gauge

glass.  Push both packings about an

inch up the gauge glass.

7)

Gently insert one end of the

glass into the top gauge fitting.

Keeping the glass inside the top fit-

ting, gently rotate the top gauge fit-

ting clockwise until vertically aligned

with the bottom gauge fitting, then

inset glass into bottom fitting until

glass bottoms out on the shoulder

inside the bottom fitting.

8) 

Carefully raise glass about 1/16”

and slide lower glass packing down

until the glass packing contacts the

lower gauge fitting.  

DO NOT

allow

the glass to remain in contact with

any metal!

9)

Carefully slide upper glass pack-

ing up as far as possible.

10)

Hand tighten both glass packing

nuts, then tighten 1/2 turn more by

wrench.  Tighten only enough to pre-

vent leakage.  

DO NOT OVER

TIGHTEN! 

If any leakage should

occur, tighten slightly, a quarter turn

at a time, checking for leakage after

each turn.

11)

Install the protective guard, and

utilize automatic ball checks where

necessary to help prevent injury in

case of glass breakage.

WARNING

Improper installation or mainte-

nance of gauge glass and connec-

tions can cause immediate or

delayed breakage resulting in bod-

ily injury and/or property damage.

Gauge Glass

Top Gauge

Fitting

Guard Rod

Glass Packing Nut

Friction Washer

Glass Packing

Bottom Gauge

Fitting

Vessel

 Wall

Drain

 Valve

B

A

Description/Instructions

Содержание FB-A 10

Страница 1: ...s HP to 60 HP Serial Number _______________________________ Model Number _______________________________ Fulton Order Number _______________________________ Sold To _______________________________ Job...

Страница 2: ......

Страница 3: ...sheen or foam should be visible Iron Take a water sample Hold the sample against a white background The water should have no visible yellow red or orange tinge ND None Detected Parameter Carbon Steel...

Страница 4: ......

Страница 5: ...s d ASME hydrostatic test inspection e Electrical components inspection f Operating test g Final Engineering Inspection h Crating inspection NOTE The installation of the Fulton Gas Fired Steam Boiler...

Страница 6: ......

Страница 7: ...r Intake UL and MEA Approved Corrosion of Flue Pipe Installation Checkpoints Cleaning the Pressure Vessel Operation Starting the Gas Fired Boiler Gas Burner Set Up Gas Burner Set Up For Boilers Equipp...

Страница 8: ...2 G 1 01...

Страница 9: ...Safety Warnings Precautions 1 3 G 1 01...

Страница 10: ...4 G 1 01...

Страница 11: ...d be cleaned CAUTION Do not store halogenated hydrocar bons near or in the boiler room NOTE a The fused disconnect switch that controls the feed water pump should be kept in the on position at all tim...

Страница 12: ...6 G 1 01...

Страница 13: ...7 G 1 01 Description Instructions LE...

Страница 14: ...8 G 1 01...

Страница 15: ...18 5 19 5 19 5 19 5 19 5 MM 470 470 495 495 495 495 J Blowdown Outlet IN 15 25 15 15 16 5 16 5 16 5 MM 387 381 381 420 420 420 K Water Column Extension IN 14 14 14 14 14 14 MM 355 355 355 355 355 355...

Страница 16: ...3 HR 384 403 606 807 1009 1210 9 13 w c req d M3 HR 10 8 11 4 17 2 22 9 28 6 34 3 Natural Gas Boiler IN 1 1 1 1 25 1 25 1 5 Connection Size Std CSD 1 MM 25 25 25 32 32 38 Oil Inlet Size IN 1 4 1 4 1 4...

Страница 17: ...11 G 1 01 Operation LE...

Страница 18: ...12 G 1 01...

Страница 19: ...ay not fire at the first attempt due to air which must be purged from the gas lines This will result in the burner flame program mer going to lockout Repeat the procedure for starting the burner f The...

Страница 20: ...14 G 1 01...

Страница 21: ...15 G 1 01 Maintenance LE...

Страница 22: ...16 G 1 01...

Страница 23: ...gas regulator until last elbow pressure matches the test fire sheet NOTE Adjust air accordingly to ensure stable combustion during gas adjustments c Adjust air setting until combus tion readings are w...

Страница 24: ...lace 3 Transformer Check voltage between transformer leads at terminal block to be sure transformer is being powered 4 Flame Safeguard Check voltage between ignition terminal and neutral Control Check...

Страница 25: ...odes Check electrodes for carbon buildup and clean if necessary Check for proper adjustment Readjust if necessary Check for cracks in porcelain if found replace 4 Scanner Check for dirt on flame scann...

Страница 26: ...nd clean Check for proper location of detector 4 Draft Check draft with a gauge Draft should be a 02 to 04 W C with burner off or 04 to 06 when operating May need to install a barometric damper 5 Nega...

Страница 27: ...when operating May need to install a barometric damper Boiler pushing water 1 Steam Traps Chech traps Clean or replace as necessary with the steam 2 Too much boiler Dump return tank and flush system...

Страница 28: ...present but motor does not run replace it Low Fuel pressure 1 Gas pressure regulator Check and replace Boiler Flooding 1 Pump does not shut off Dirty probes Clean or replace as necessary 2 Relay faile...

Страница 29: ...23 G 1 01 Parts LE...

Страница 30: ...24 G 1 01...

Страница 31: ...5 HP 2 91 2 12 253 Furnace Burner Tile 10 HP 2 91 2 12 221 Furnace Burner Tile 15 HP 2 91 2 12 254 Furnace Burner Tile 20 30 HP 15 6 8 5 21 6009 Burner Scroll 9 5 HP 30 13 6 5 21 6010 Burner Scroll 1...

Страница 32: ...26 G 1 01...

Страница 33: ...Boiler Description Instructions Gas Fired Boiler 2 27 G 1 01...

Страница 34: ...QQQQQQQQQQQQQQQQQ QQQQQQQQQQQQQQQQQQQQQ Transformer Scroll Gaskets Steam Gauge Assembly Gauge Glass Valve To O P C To H P C Burner Motor Gauge Glass Valve Gauge Glass And Protector Water Column Contro...

Страница 35: ...9 85 MM 1070 1320 1575 1473 1600 1675 1728 1867 2007 2159 H Feedwater Inlet IN 27 33 33 5 33 33 5 34 34 34 35 35 MM 685 840 851 840 851 865 865 865 890 890 I Handholes IN 19 19 19 19 19 19 19 19 20 20...

Страница 36: ...257 398 419 628 837 1047 1256 2093 2511 7 11 w c req d M3 HR 4 8 7 1 11 3 11 9 17 8 23 7 29 7 35 4 59 3 71 1 Natural Gas ICX FT3 HR 159 242 384 403 606 807 1009 1210 7 11 w c req d M3 HR 5 6 6 9 10 8...

Страница 37: ...30 G 1 01 Description Instructions I E K K J K D C H B A G F...

Страница 38: ...per size to ensure adequate gas supply to the gas head assembly Consult your gas company for specific recommen dations e For natural gas a pressure of 7 to 11 178mm to 279mm of water col umn pressure...

Страница 39: ...NOTE Where a condensate return tank is to be fitted this should 1 Be vented to a safe location and 2 Have a capacity sufficient to satisfy boiler consumption as well as maintain proper return tank tem...

Страница 40: ...alve is supplied with the unit b In a closed system an end of the line trap should be installed c There are three blow off valves on the boiler the main valve at the rear of the boiler the gauge glass...

Страница 41: ...a pipe size equal to or greater than that of the valve outlet Use schedule 40 discharge pipe only Do not use schedule 80 extra strong or double extra strong dis charge pipe or connections It must be...

Страница 42: ...25 60 1 25 2 When feeding the boiler using a return system the city water pressure should not exceed 40 PSI A pres sure reducing valve should be installed a head of the return tank when above this pr...

Страница 43: ...g from the fittings and place them in the same order on to both ends of the gauge glass Push both packings about an inch up the gauge glass 7 Gently insert one end of the glass into the top gauge fitt...

Страница 44: ...te the boiler metal and are usually covered with tuber cles of iron oxide Once pitting starts it may be extremely hard to arrest Pitting can proceed at a surprisingly rapid rate and can occur not only...

Страница 45: ...king a bot tle containing boiler water If oil is present foam will result To ensure the foaming is being caused by oil add a small amount of powdered activated carbon to the bottle con taining the boi...

Страница 46: ...one at a high er level in the boiler room wall This will provide a flow of air to exhaust the hot air from the boiler room Room temperature not to exceed 100 F c The following openings are recommended...

Страница 47: ...ack to avoid hav ing too great a load imparted to the flue outlet connection of the boiler e The proper flue size and draft control is most important for proper burner operation The flue must be as la...

Страница 48: ...equal to or greater than 50 square inches 3 A mesh screen shall be affixed to the air inlet with openings of approxi mately 1 2 x 3 4 4 The total length from outdoors to the boiler intake shall not e...

Страница 49: ...m safety valve opening 4 The mixture of washing soda to water is as follows Boiler Size Soda 4 6 1 lb 454g 10 15 2 lb 908g 20 30 3 lb 1362g 40 50 3 1 2 lb 1589g 60 4 lb 1816g 5 Replace the steam safet...

Страница 50: ...42b G 1 01...

Страница 51: ...43D G 1 01 Operation 3...

Страница 52: ...43b G 1 01...

Страница 53: ...feed valve on the boiler 5 Open valves on makeup water line to return if return system is used 6 Place feedwater pump fused switch in the on position NOTE a The fused disconnect switch that controls t...

Страница 54: ...ve giving a main flame e Fulton 4 30 h p natural gas fired boilers can be equipped with flame rods or UV scanners f All Fulton propane or butane boil ers and 50 and 60 HP Fulton natural gas boilers ar...

Страница 55: ...per combustion characteristics f The modulating burner will have a modulation lock switch in the panel box to enable you to lock the firing sequence anywhere along the firing rate from low to high g D...

Страница 56: ...high low gas valve e The end of the linkage arm that goes to the gas valve will have a notch on both sides of where the swivel collar should be centered This setting was based on factory test fire con...

Страница 57: ...proportionately divide the air to the center or outer fire chamber By mov ing the damper closed the air is forced to the outside of the fire chamber with less air going down the blast tube area By pul...

Страница 58: ...ssure falls below a predetermined level e Sight Glass Isolation Valves The brass sight glass isolation valves are equipped with an internal ball check In the event that a sight glass should break the...

Страница 59: ...Maintenance 4 5 G 1 01...

Страница 60: ...51 G 1 01...

Страница 61: ...QQQQQQQQQQQQQQQQQQQQQ Transformer Scroll Gaskets Steam Gauge Assembly Gauge Glass Valve To O P C To H P C Burner Motor Gauge Glass Valve Gauge Glass And Protector Water Column Control Box High Density...

Страница 62: ...s in water column Make sure there is no pressure on the boiler during the removal of the probes Remove one probe using a 7 8 socket clean with very fine emory cloth and replace it before removing anot...

Страница 63: ...pplies may need adjusting If a flame rod is cracked or broken the porcelain will have to be replaced to get a proper signal Flame Scanner Adjustments for Fulton Gas Fired Steam Boilers a Flame scanner...

Страница 64: ...tory is to be changed the bottom refractory need not be broken f Round and bevel the outer edges of the new refractories g The bottom refractory has the largest hole while the top refractory has the s...

Страница 65: ...ay make sure ignition and burner are working properly f Check water level in sight glass g Check to be sure feed water pump is working h For float type water level control blow down float chamber Reco...

Страница 66: ...pressure on the boiler dur ing the removal of the probes 6 Check refractories for soot or breakage and inspect the stainless steel ring 50 and 60 HP only 7 With the boiler under no more than 15 PSI pr...

Страница 67: ...ter a new Fulton Boiler has been in operation for several months pieces of burned metal will be found in the space at the bottom of the boiler These pieces of metal are the remains of a light gauge me...

Страница 68: ...oltage between ignition terminal and neutral Control Check must be made before control locks out on safety If no power replace control 5 Faulty Air Switch Check for bad air switch by jumpering the two...

Страница 69: ...rodes Check electrodes for carbon buildup and clean if necessary Check for proper adjustment Readjust if necessary Check for cracks in porcelain if found replace 4 Flame Rod Adjustment Check flame rod...

Страница 70: ...essary Check for proper adjustment Readjust if necessary Check for cracks in porcelain if found replace 3 Flame rode adjustment Check flame rod for carbon buildup and clean if or UV Scanner necessary...

Страница 71: ...water treatment company 5 Too much water Have water tested by water treatment company softener high PH 6 Too much of a load Check total equipment horsepower required against horsepower of boiler bein...

Страница 72: ...Water pump will not 1 Scale on probes Check and clean or replace as necessary come on at times 2 Bad Pump Contactor Check to see if contactor is being powered Check to see if contactor coil is pulling...

Страница 73: ...Parts 5 6 G 1 01...

Страница 74: ...F Edge second flue gas pass rib heat transfer pattern and cannot be converted to fire 2 oil These boilers will also require use of the Edge cleanout brush in lieu of the standard The Edge cleanout bru...

Страница 75: ...ure that the full information given in the Parts List is supplied together with the following details as shown on your boiler identification plate 1 Boiler Number 2 Boiler Type 3 Electrical Specificat...

Страница 76: ...0 355 Flue Cover Ring 15 HP 20 5 9 32 5 10 357 Flue Cover Ring 20 HP 21 9 55 5 10 359 Flue Cover Ring 30 HP 25 11 36 5 10 360 Flue Cover Ring 40 60 HP 40 18 18 5 12 001 Bottom Cleanout Access Plate wi...

Страница 77: ...air Kits 40 60 HP 9 5 4 32 2 21 053 6 Stack Connection 4 10 HP 6 5 2 95 2 21 054 8 Stack Connection 15 HP 7 3 18 2 21 055 10 Stack Connection 20 HP 7 5 3 41 2 21 056 12 Stack Connection 30 60 HP 8 3 6...

Страница 78: ...ll Casting 9 5 HP 14 6 36 2 11 123 Burner Scroll Casting 4 15 HP 30 13 64 5 20 059 Burner Scroll Casting 20 HP 35 15 91 5 20 060 Burner Scroll Casting 30 HP 40 18 18 5 20 061 Burner Scroll Casting 40...

Страница 79: ...55C 1 5 2 27 2 40 252 Gas Valve Body P O C V5055C 1 1 4 5 1 2 32 2 40 253 Gas Valve Body P O C V5055C 1 1 2 4 7 2 14 2 40 254 Gas Valve Body P O C V5055C 2 9 3 4 23 2 40 214 Actuator for 2 2 1 2 and 3...

Страница 80: ...Orifice 10 HP 2 0 91 7 20 033 Propane Orifice 15 HP Post 2 89 1 2 0 91 7 20 063 Propane Orifice 15 HP Pre 2 89 1 1 4 2 5 1 14 7 20 064 Propane Orifice 20 HP 3 1 36 7 20 065 Propane Orifice 30 HP 3 1...

Страница 81: ...2 27 7 54 1005 Gas Train Assembly 30 HP Natural Gas 27 12 27 7 54 1006 Gas Train Assembly 40 50 HP Natural Gas 70 31 82 7 54 1007 Gas Train Assembly 60 HP Natural Gas 70 31 82 7 54 1050 Gas Train Asse...

Страница 82: ...mn 11 1 4 0 3 0 14 2 20 017 Low Water Probe in Boiler 17 1 8 0 5 0 23 2 21 012 Probe Cover 2 1 0 45 2 21 013 Probe Cover 4 1 0 45 2 30 398 1 4 Male Female Ball Valve for Water Column 0 6 0 27 2 40 021...

Страница 83: ...BSC 24 0 45 0 2 2 40 572 Overload AB BSB 42 0 45 0 2 2 40 573 Overload AB BSB 60 0 45 0 2 2 40 574 Overload AB BSB 80 0 45 0 2 2 40 566 Overload AB BSB 90 0 45 0 2 2 40 200 Motor Starter Relay 120V 20...

Страница 84: ...e Blowdown Valve 200 8 4 3 82 2 30 007 1 Quick Action Blowdown Valve 13 5 91 2 30 014 1 1 4 Quick Action Blowdown Valve 14 6 36 2 30 023 1 1 2 Quick Action Blowdown Valve 23 10 45 2 40 133 Timer for A...

Страница 85: ...5 0 23 2 30 334 0 60 PSI Steam Pressure Gauge 0 5 0 23 2 30 333 0 200 PSI Steam Pressure Gauge 0 5 0 23 2 30 332 0 300 PSI Steam Pressure Gauge 0 5 0 23 2 30 327 0 600 PSl Steam Pressure Gauge 0 5 0...

Страница 86: ...r Gauge Glass Rubber 2 2 12 000020 Water Gauge Glass Fiber 1 2 20 000019 Ignition Electrode 1 5 10 000397 Tee Handle Wrench 1 4 30 000052 Set of 4 Plugs and Probes 2 12 515 Burner Plate Gasket 4 HP Ga...

Страница 87: ...0 60 HP 1 0 45 2 12 518 Top Plate Gasket 4 HP Old Style 1 0 45 2 12 519 Top Plate Gasket 4 15 HP 1 0 45 2 12 520 Top Plate Gasket 20 30 HP 1 0 45 2 12 521 Top Plate Gasket 40 60 HP 1 0 45 4 12 522 9 5...

Страница 88: ...79 G 1 01 Parts...

Страница 89: ...40 50 2 30 425 9 3 16 X 2 1 2 x 1 LP N Gas 50 60 60 The correct part number is located on the back of the fan plate Part No Ignition Transformer 4 2 40 082 120 60 1 2 40 083 240 60 1 2 40 084 120 50 1...

Страница 90: ...81 G 1 01 Parts Gas Burner Ignition Assembly Gas Burner Components...

Страница 91: ...0 116 Main Gas Manual Shut Off Valve 60 2 30 104 Main Gas Pressure Regulator 2 4 15 2 30 105 Main Gas Pressure Regulator 20 2 30 107 Main Gas Pressure Regulator 30 50 2 30 108 Main Gas Pressure Regula...

Страница 92: ...83 G 1 01 Parts 1 2 9 10 11 6 8 3 2 5 4 7 6 8 9 10 11 1 Gas Head Assembly CSD 1 4 to 50 HP Gas Head Assembly CSD 1 60 HP...

Страница 93: ...2 40 201 Motor Starter Relay 220V 20 AMP 4 50 2 40 203 Motor Starter Relay 220V 30 AMP 4 50 Part No Flame Safeguard Control HP 2 40 260 RM7895F Programmer 4 50 2 40 262 RM7800M Programmer 60 100 2 40...

Страница 94: ...ss Water Gauge Glass Gasket 4 4 100 2 12 019 Rubber Water Gauge Glass Gasket 5 4 100 2 35 514 Brass Packing Nut for Gauge Glass Valve 6 4 100 2 30 330 Gauge Glass Protector Rods 7 4 100 2 12 022 Lucit...

Страница 95: ...Warranty 6 8 G 1 01...

Страница 96: ...87 G 1 01...

Страница 97: ...manufacturers and the commissioning agency has successfully completed and returned the equipment Installation and Operation Checklists to Fulton s Quality Assurance department General Fulton shall be...

Страница 98: ...89 G 1 01...

Страница 99: ...nt from the factory provided this equipment has been installed operated and maintained by the buyer in accordance with approved practices and recommendations made by both Fulton and the component manu...

Страница 100: ...91 G 1 01...

Страница 101: ...Component Data Sheets 7 G 1 01...

Страница 102: ......

Отзывы: