32-G 1/01
Description/Instructions
Vent
Vent
Return
Cold
Water
Supply
Sight
Glass
Union
Pump/
Strainer
Thermometer
Aquastat
Drain
Condensate
Return
Tank
Blowdown
Separator
Outlet
To Drain
Check
Valve
Shut
Off
Valve
Cold Water
Inlet
Basic Boiler,
Condensate Tank,
and Blow off
Separator
NOTE
Where a condensate return tank is
to be fitted, this should:
1) Be vented to a safe
location, and
2) Have a capacity sufficient to
satisfy boiler consumption as well
as maintain proper return tank
temperature.
3) Vent pipe should not be down-
sized (this may cause pressure
build up in the condensate tank).
4) Return pipes must not be insu-
lated. This can cause overheating
the return system, causing a vapor
lock in the pump.
5) See Return System Instruction
Manual for detailed instructions.
Содержание FB-A 10
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ...2 G 1 01...
Страница 9: ...Safety Warnings Precautions 1 3 G 1 01...
Страница 10: ...4 G 1 01...
Страница 12: ...6 G 1 01...
Страница 13: ...7 G 1 01 Description Instructions LE...
Страница 14: ...8 G 1 01...
Страница 17: ...11 G 1 01 Operation LE...
Страница 18: ...12 G 1 01...
Страница 20: ...14 G 1 01...
Страница 21: ...15 G 1 01 Maintenance LE...
Страница 22: ...16 G 1 01...
Страница 29: ...23 G 1 01 Parts LE...
Страница 30: ...24 G 1 01...
Страница 32: ...26 G 1 01...
Страница 33: ...Boiler Description Instructions Gas Fired Boiler 2 27 G 1 01...
Страница 37: ...30 G 1 01 Description Instructions I E K K J K D C H B A G F...
Страница 50: ...42b G 1 01...
Страница 51: ...43D G 1 01 Operation 3...
Страница 52: ...43b G 1 01...
Страница 59: ...Maintenance 4 5 G 1 01...
Страница 60: ...51 G 1 01...
Страница 73: ...Parts 5 6 G 1 01...
Страница 88: ...79 G 1 01 Parts...
Страница 90: ...81 G 1 01 Parts Gas Burner Ignition Assembly Gas Burner Components...
Страница 95: ...Warranty 6 8 G 1 01...
Страница 96: ...87 G 1 01...
Страница 98: ...89 G 1 01...
Страница 100: ...91 G 1 01...
Страница 101: ...Component Data Sheets 7 G 1 01...
Страница 102: ......