Full Gauge MT-512e Log Скачать руководство пользователя страница 1

5. INDICATIONS AND KEYS

DIGITAL INDICATOR AND CONTROLLER FOR 

HEATING OR REFRIGERATION WITH NATURAL DEFROST 

THROUGH COMPRESSOR SHUTDOWN AND 

INTERNAL DATALOGGER

MT-512

e

 

Log

Ver

.09

Control functions 

shutdown

Function 

lock

Serial 

programming

Degrees 

of protection

Manual 

defrost

IP 65

FRONT

Supervisory 

system

Datalogger

LOG

Power supply

Control temperature

Operating humidity
Dimensions (mm)

76 x 34 x 77 mm (WxHxD)

MT-512E Log

 115 or 230 Vac ±10%(*) (50/60 Hz)

MT-512EL Log

 12 or 24 Vac/dc +10%(*)

 

 

 

-50 to 105ºC (-58 to 221°F)(**)

Operating temperature

0 to 50 ºC / 32 to 122°F

Maximum output current

NO -

16A / 2HP

NC - 

500W / 1/10HP

10 to 90% RH (without condensation)

Temperature unit indication LED

MT-512

e

 

Log

Upper Key

Lower Key

Set Key

User-friendly

Menu Key (Flatec)

Cooling indication LED

Heating indication LED

Defrost indication LED

Functions lockdown indication LED

Control functions OFF indication LED

Maximum consumption of device

1.5 VA

(*)

Admissible variation in relation to the voltage rating.

(**)

This device can measure and control temperatures of up to 200° C when used in conjunction with a model SB59 silicon 

sensor cable (sold separately).

Note: 

Sensor cable length can be increased to up to 200 meters by the user by using a PP 2 x 24 AWG cable.

Image I: MT-512E Log - 115Vac

1. DESCRIPTION

2. SAFETY RECOMMENDATIONS

3. APPLICATIONS

4. TECHNICAL SPECIFICATIONS

Designed for cooling or heating application. 

MT-512

e

 

Log

 is equipped with 1 powerful 2HP relay, 1 

temperature sensor, 1 digital input, data logger, cyclic time for natural defrost, IP65 frontal, min-max 
temperature record, sensor response time control, fast freezing mode, tamper-proof function, control 
functions  shutdown  and  RS485  serial  communication  port  for  Sitrad  real-time  monitoring  and 
management.
Product conforming to UL Inc. (United States and Canada).

 
- Check the controller for correct assembling;
- Make sure that the power supply is off and that it is not turned on during the controller installation;
- Read the present manual before installing and using the controller;
- Use adequate Personal Protective Equipmenet (PPE); 
- For application at sites subject to water spills, such as refrigerated cabinets, install the protecting vinyl 
supplied with the controller;
-  For  protection  under  more  critical  conditions,  we  recommend  the  Ecase  cover,  which  we  make 
available as an optional item (sold separately);
- The installation procedures should be performed by a qualified technician.

• Refrigerated displays
• Walk-in coolers
• Hot cabinets
• Greenhouses

115 Vac

Image III: MT-512EL Log - 12Vac/dc

6. WIRING DIAGRAM

6.1. Identifications (see Images I to IV)

-

 

Image I:

 MT-512E Log, supplied at 115 Vac. 

-

 

Image II:

 MT-512E Log, supplied at 230 Vac. 

- Image III:

 MT-512EL Log, supplied at 12 Vac/dc. 

- Image IV:

 MT-512EL Log, supplied at 24Vac/dc.

Image

MT-512E Log

 II: 

 - 230 Vac

230 Vac

POWER

12Vac/dc

Image IV: MT-512EL Log - 24Vac/dc 

POWER

24Vac/dc

IMPORTANT

SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER TERMINALS;

THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE IN THE CONNECTION AT INSTRUMENT
TERMINALS:

6.2. Temperature sensor connection

- Connect the sensor wires to terminals ‘1 and 2’: the polarity is not relevant.
- Length of the sensor cables can be increased by user himself to up to 200 meters, using a PP 2x24 
AWG cable.
- For immersion in water, use a thermowell (Image VI - item 13), available in the Full Gauge Controls 
product line (sold separately).

CONTROLLER

WIRING

TERMINALS

TEMPERATURE

SENSOR

WIRING

TERMINALS

LOAD

CONTROLLER

WIRING

TERMINALS

LOAD

TEMPERATURE

SENSOR

WIRING

TERMINALS

CONTROLLER

WIRING

TERMINALS

TEMPERATURE

SENSOR

WIRING

TERMINALS

LOAD

LOAD

TEMPERATURE

SENSOR

CONTROLLER

WIRING

TERMINALS

WIRING

TERMINALS

D1

A

B

NC

D1

A

B

D1

A

B

D1

A

B

NC

NC

NC

POWER

GRID

}

POWER

GRID

}

POWER

GRID

}

POWER

GRID

}

evolution

 

 

S u r g e P r o t e c t i v e

Device (SPD)

(sold separately)

W i r i n g   d i a g r a m   f o r    

instalation  of  SPD  in   

magnectic contactor

A1 and A2 are the terminals of 
the contactor coil.

A1

A2

W i r i n g   d i a g r a m   f o r  

instalation  of  SPD  in  line 

with loads

For  direct  drive  take  in  to 
consideration  the  specified 
maximum current.

LOAD

SPD

SPD

Cutout dimensions (mm)

 

71 ± 0,5 x 29 ± 0,5 mm (see image V)

NO

COMMON

NO

COMMON

NO

COMMON

NO

COMMON

MT512ELOG9-02T

-15255

MT-512

Log

MT-512

Log

E251415

Отзывы: