TEMPERATURE AND HUMIDITY DIGITAL

CONTROLLER WITH SERIAL COMMUNICATION

1. DESCRIPTION

MT-531Ri plus

is an instrument that indicates and controls the environment temperature and

humidity, indicated for low and average relative air humidity (from 20 to 85%, without condensation) and
temperature of -10 to 70ºC. Its sensors of temperature and humidity are joined in an only bulb, that
reduces the space in wiring of the installation.

The instrument has serial communication for connection with the

via Internet.

Product complies with UL Inc. (United States and Canada).
Producto de conformidad con CE (Unión Europea) y UL Inc. (Estados Unidos y Canadá).

®

SITRAD

2. APPLICATION

3. TECHNICAL SPECIFICATIONS

• Poultry farm
• Humidificators/dehumidificators
• Grains drying
• Laboratories
• Surgical rooms
• Climatized cellars
• Information technology centers

MT-531Ri plus - 115 or 230 Vac ±10%(50/60 Hz)
MT-531RiL plus - 12 or 24 Vac/dc

-10 to 70.0 ºC (with resolution of 0.1°C)
14 to 158 ºF (with resolution of 1°F)

20 to 85%RH (with resolution of 0.1%UR)

5(3)A/250Vac 1/8HP (each output)

71 x 28 x 71 mm

0 to 50°C

32 to 122°F

10 to 90% RH (without condensation)

- Power Supply:

- Control Temperature:

- Control Humidity:
- Load current:
- Dimensions:
- Operation temperature:

- Operation humidity:

4.2 - Parameters configuration

- Access the function F01 pressing simultaneously the keys

and

for 2 seconds until appearing

, releasing after that. Soon it will appear

, and then press

(short touch).

- Use the keys

and

to enter acess code (123) and, when ready press

to confirm.

- Use the keys

and

to access the desired function.

-After selecting the function, press

(short touch) to visualize the value configured for that function.

- Use the keys

and

to change the value, and when ready, press

to memorize the configured

value and return to the menu of functions.
- To leave the menu of functions and return to normal operation, press

until appear

.

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

4. CONFIGURATIONS

4.1 - Temperature and humidity adjust (SETPOINT):

- Press

for 2 seconds until

appears, then release it. The indication

and the adjusted

temperature for THERM output will appear.
- Use the keys

and

to change the value and then press

to record it.

- Now

and adjusted humidity for HUMID output will appear.

- Use the keys

and

to change the value and then press

again.

- If the parameter F14 is configured as thermostat or humidistat the following message will appear:

or

.

- Use the keys

and

to change the value for theAUX output and then press

to record it.

SET

SET

SET

SET

Description

Fun

Access code: 123 (one hundred and twenty-three)

hermostat operation mode (THERM output)

Minimum setpoint allowed to the user (thermostat)

Maximum setpoint allowed to the user (thermostat)

Control differential (hysteresis) of the thermostat

Minimum delay to turn the thermostat output on

Humidistat operation mode (HUMID output)

Minimum setpoint allowed to the user (humidistat)

Maximum setpoint allowed to the user (humidistat)

Control differential (hysteresis) of the humidistat

Minimum delay to turn the humidistat output on

Humidity output (time on)

Humidity output (time off)

Auxiliary output operation mode (AUX)

Minimum setpoint allowed to the user (AUX output)

T

4.4 - Parameters description

CELSIUS

FAHRENHEIT

Min.

-99

0 - refrig.

-10.0

-10.0

0

0

0 - dehum.

0

0

0

0

0

0

0

0

Max.

999

1 - heat

70.0

70.0

20.0

999

1 - hum.

100

100

20.0

999

999

999

5

100

Unit

-

-

°C

°C

°C

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Satandar

-

-10.0

70.0

15

0

0 - refrig.

1 - hum.

0

100

5

0

5

5

5

0

Mín

-99

0 - refrig.

14

14

0

0

0 - dehum.

0

0

0

0

0

0

0

0

Máx

999

1 - heat

158

158

36

999

1 - umid.

100

100

20.0

999

999

999

5

100

Unid

-

-

°F

°F

°F

seg.

-

%RH

%RH

%RH

sec.

sec.

sec.

-

-

Padrão

-

0 - refrig.

14

158

3

0

1 - hum.

0

100

5

0

5

5

5

0

Maximum setpoint allowed to the user AUX output

Control differential (hysteresis) of the AUX output

Minimum delay to turn the AUX output on

AUX output (time on)

AUX output (time off)

Minimum delay to turn the AUX output on (alarm mode)

Acting point of temperature Buzzer (inferior limit)

Acting point of temperature Buzzer (superior limit)

Acting point of

Buzzer (inferior limit)

Acting point of

Buzzer (superior limit)

Buzzer time on

Buzzer time off

Inhibition time of Buzzer during electrical supply

(

)

Buzzer operation mode

humidity

humidity

Low room temperature alarm

High room temperature alarm

Low room humidity alarm

High room humidity alarm

0

0

0

0

0

-10.0

-10.0

0

0

0

0

-10.0

-10.0

0

0

0

0

0

100

20.0

999

999

999

70.0

70.0

100

100

999

1

70.0

70.0

100

100

999

999

999

-

-

sec.

sec.

sec.

°C

°C

%RH

%RH

min.

-

°C

°C

%RH

%RH

sec.

sec.

min.

100

5

0

5

5

-10.0

70.0

0

100

0

1

-10.0

70.0

0

100

1

1

0

0

0

0

0

0

14

14

0

0

0

0

14

14

0

0

0

0

0

100

20.0

999

999

999

158

158

100

100

999

1

158

158

100

100

999

999

999

100

5

0

5

5

14

158

0

100

0

1

14

158

0

100

1

1

0

-

-

sec.

sec.

sec.

°F

°F

%RH

%RH

min.

-

°F

°F

%RH

%RH

sec.

sec.

min.

Display mode

Temperature display offset

Humidity display offset

Network equipment address RS-485

0

-5.0

-20.0

0

2

5.0

20.0

247

-

°C

%RH

-

0

0

0

1

0

-9

-20.0

0

2

9

20.0

247

0

0

0

1

-

°F

%RH

-