Full Gauge Controls MT-518Ri Скачать руководство пользователя страница 1

1. DESCRIPTION

MT-518Ri

 is a temperature controller with two outputs that can be configured as double stage of 

refrigeration, double stage of heating or heating and refrigeration. Its second output also can be 
configured for alarm intra, extra-range or, even , relative extra-range.
Product complies with CE (European Union) and UL Inc. (United States and Canada).

2. APPLICATION

• Winter/Summer automatic system in air conditioning

3. TECHNICAL SPECIFICATIONS

- Power supply:

MT-518Ri       115 or 230 Vac ± 10% (50/60Hz)
MT-518RiL       12 or 24 Vac/dc

- Control temperature: 

-50 to 105ºC (decimal resolution between -10 and 100 ºC)

- Input:

 NTC sensor

- Load current: 

8(3)A/250Vac 1/4HP each output

- Dimensions: 

71 x 28 x 71mm

- Operation temperature: 

0 to 50 ºC

- Operation humidity: 

10 to 90% RH (without condensation)

UL-Underwriters Laboratories

MT-518Ri

DIGITAL TEMPERATURE CONTROLLER

  WITH TWO STAGES 

Ver. 12

M

T

5

1

8

V

1

2

-0

1

T

-1

0

8

7

3

CLASSIFICATION ACCORDING TO IEC60730-2-9 STANDARD:
- Temperature limit of the installation surface:

 50°C

- Type of construction: 

Built-in electronic controller

- Automatic action: 

Type 1

- Control of pollution: 

Level 2

- Impulse voltage: 

1,5kV 

- Temperature for the test of sphere pressure: 

75°C and 125°C

- Insulation: 

Class II

4. CONFIGURATIONS

4.1 - Control temperatures adjust (SETPOINTS)

- Press        for 2 seconds until          appears, then release it.          will appear and the adjusted 
temperature for 1st stage.  
- Use the keys         and         to change the value and then press          to record it.
- Now                        and the adjusted temperature for 2st stage will appear. ( only if F08 = 0 or F08 = 1).
- Use the keys         and         to change the value and then press          again.

SET

SET

SET

Description

Min

Max

Unit

Fun

4.2 - Parameters table

Configuration parameters protected by access code.

Note: 

F02 function allows to correct eventual shuting lines in the reading, proceeding of the sensor 

exchange or alteration of sensor length.

(

4

)

2nd stage operation 

mode:

0 - refrigeration
1 - heating
2 - alarm (inside of 
range)
3 - alarm (outside of 
range)
4 - relative alarm 
(outside of range)

(1)

First stage 

operation mode:

0 - refrigeration
1 - heating

F01

F02

F03

F04

F05

F06

F07

F08

F09

F10

F11

F12

F13

F14

F15

Access code 123 (one hundred and twenty-three)

Display (offset) 

(1)

1st stage operation mode

Minimum setpoint allowed to the end user (1st stage)

Maximum setpoint allowed to the end user (1st stage)

Control differential (hysteresis) of 1st stage

Minimum delay to turn on the 1st stage output

(2)

2nd stage operation mode

Minimum setpoint allowed to the end user (2nd stage)

Maximum setpoint allowed to the end user (2nd stage)

Control differential (hysteresis) of 2nd stage

Minimum delay to turn on the 2nd stage output

 Alarm delay when the instrument is powered on

Alarm output time on

Alarm output time off

-

-5.0

0

-50

-50

0.1

0

0

-50

-50

0.1

0

0

0

0

-

5.0

1

105

105

20.0

999

4

105

105

20.0

999

999

999

999

-

°C

-

°C

°C

°C

sec.

-

°C

°C

°C

sec.

min.

sec.

sec.

4.3 - Parameters alteration

Access the function F01 pressing simultaneously the keys      and      for 2  seconds until appearing
           , releasing after that. Soon it will appear            , and then press         (short touch). 
- Use the keys        and        to enter with the access code (123), and then press         to enter.
- Use the keys        and        to access the desired function.
- After selecting the function, press         (short touch) to display the  configured value for that function.
- Use the keys        and        to change the value and then press         to record the new value and return 
to the functions menu.
- To return to the normal operation, press         until            appear.

5. FUCTIONS WITH FACILITATED ACCESS

Registers of minimum and maximum temperatures 

Press     . The minimum registered temperature appears and after soon the maximum registered 
temperature.

Nota: 

To reset the registers, keep the key     pressed during the visualization of the minimum and 

maximum temperatures until            to be showed.            

SET

SET

SET

SET

SET

If the instrument is configured as alarm, set the F09 and F10 act points normally and ignore 

ST2

 and 

F11. If the temperature goes out the specified range and ring the alarm, press        and         to inhibit the 
sound

.

6. SIGNALING

ST1

-

 

1st stage output on

ST2

-

 

2nd stage output on

- Detached sensor or temperature outside the specified range

With F08=4 the ST2 output is activated when the temperature reaches a value equal 

ST1

 minus the 

configurated value in F09 (

ST1

-F09), or when the temperature reaches a value equal 

ST1

 plus the 

configurated value in F10 (

ST1

+F10)

Ex. :

- Temperature in ST1 = 25 ºC

- Value in F08 = 4 

- Value in F09 = 2

- Value in F10 = 5

The 

ST2

 output will be kept on when the temperature is below 23 ºC (25-2) or above 30 ºC (25+5). If 

ST1 

value is changed to 24 ºC the alarm values will be automatically modified to 22 and 29 ºC.
IF the functions F14 and F15 are set with zero, the 

ST2

 output will be kepped on while the alarm 

condition persist.

SET

enso

S

r

Power 

supply

Load 1

CO

M

M

ON

 

Loads

supply

ST

(N

O)

ST

(N

O)

1

2

3

4

5

6

7

8

9

10 11 12

115 V

(12 V)

230 V

(24 V)

0

72 mm

29

 m

m

7. WIRING DIAGRAM

7 - 8
7 - 9

115V
230V  

12V
24V

MT-518Ri

MT-518RiL

Load 2

- Refrigerator
- Heating
- Contactor
- Solenoid

- Refrigerator
- Heating
- Contactor
- Solenoid

Load 1

Load 2

Above specified current use contactors.

Dimension of the clipping for

setting of the instrument

IMPORTANT

For more information contact our application eng. department through e-mail 

support@ fullgauge.com

 or dial +55 51 3475.3308.

According to the chapters of norm IEC 60364:  

1:

 Install protector against overvoltage on the power supply

2:

 Sensor cables and signal cables of the computer may be joined, but not in the same electric conduit 

through which the electric input and the activation of the loads run

3:

 Install transient suppresors (RC filters) parallel to the loads as to increase the product life of the 

relays.

Contact suppresor connection diagram

S

up

pr

es

or

A1

A2

A1 e A2 are the
contactor coils.

Diagram for suppresor installation

for direct drive load inputs

Load

S

up

pr

es

or

For direct activation the maximum
specified current should be taken
into consideration.

Note:

 The user can increase the length of the sensor cable to up to 200 meters, by using PP 2 X 24 AWG 

cable. For immersion in water, use thermometric well. 

PROTECTIVE VINYL:

This adhesive vinyl (included inside the packing) protects the instruments against 
water drippings, as in commercial refrigerators, for example.
Do the application after finishing the electrical connections.

1. DESCRIPTION

MT-518Ri

 is a temperature controller with two outputs that can be configured as double stage of 

refrigeration, double stage of heating or heating and refrigeration. Its second output also can be 
configured for alarm intra, extra-range or, even , relative extra-range.
Product complies with CE (European Union) and UL Inc. (United States and Canada).

2. APPLICATION

• Winter/Summer automatic system in air conditioning

3. TECHNICAL SPECIFICATIONS

- Power supply:

MT-518Ri       115 or 230 Vac ± 10% (50/60Hz)
MT-518RiL       12 or 24 Vac/dc

- Control temperature: 

-50 to 105ºC (decimal resolution between -10 and 100 ºC)

- Input:

 NTC sensor

- Load current: 

8(3)A/250Vac 1/4HP each output

- Dimensions: 

71 x 28 x 71mm

- Operation temperature: 

0 to 50 ºC

- Operation humidity: 

10 to 90% RH (without condensation)

UL-Underwriters Laboratories

MT-518Ri

DIGITAL TEMPERATURE CONTROLLER

  WITH TWO STAGES 

Ver. 12

M

T

5

1

8

V

1

2

-0

1

T

-1

0

8

7

3

CLASSIFICATION ACCORDING TO IEC60730-2-9 STANDARD:
- Temperature limit of the installation surface:

 50°C

- Type of construction: 

Built-in electronic controller

- Automatic action: 

Type 1

- Control of pollution: 

Level 2

- Impulse voltage: 

1,5kV 

- Temperature for the test of sphere pressure: 

75°C and 125°C

- Insulation: 

Class II

4. CONFIGURATIONS

4.1 - Control temperatures adjust (SETPOINTS)

- Press        for 2 seconds until          appears, then release it.          will appear and the adjusted 
temperature for 1st stage.  
- Use the keys         and         to change the value and then press          to record it.
- Now                        and the adjusted temperature for 2st stage will appear. ( only if F08 = 0 or F08 = 1).
- Use the keys         and         to change the value and then press          again.

SET

SET

SET

Description

Min

Max

Unit

Fun

4.2 - Parameters table

Configuration parameters protected by access code.

Note: 

F02 function allows to correct eventual shuting lines in the reading, proceeding of the sensor 

exchange or alteration of sensor length.

(

4

)

2nd stage operation 

mode:

0 - refrigeration
1 - heating
2 - alarm (inside of 
range)
3 - alarm (outside of 
range)
4 - relative alarm 
(outside of range)

(1)

First stage 

operation mode:

0 - refrigeration
1 - heating

F01

F02

F03

F04

F05

F06

F07

F08

F09

F10

F11

F12

F13

F14

F15

Access code 123 (one hundred and twenty-three)

Display (offset) 

(1)

1st stage operation mode

Minimum setpoint allowed to the end user (1st stage)

Maximum setpoint allowed to the end user (1st stage)

Control differential (hysteresis) of 1st stage

Minimum delay to turn on the 1st stage output

(2)

2nd stage operation mode

Minimum setpoint allowed to the end user (2nd stage)

Maximum setpoint allowed to the end user (2nd stage)

Control differential (hysteresis) of 2nd stage

Minimum delay to turn on the 2nd stage output

 Alarm delay when the instrument is powered on

Alarm output time on

Alarm output time off

-

-5.0

0

-50

-50

0.1

0

0

-50

-50

0.1

0

0

0

0

-

5.0

1

105

105

20.0

999

4

105

105

20.0

999

999

999

999

-

°C

-

°C

°C

°C

sec.

-

°C

°C

°C

sec.

min.

sec.

sec.

4.3 - Parameters alteration

Access the function F01 pressing simultaneously the keys      and      for 2  seconds until appearing
           , releasing after that. Soon it will appear            , and then press         (short touch). 
- Use the keys        and        to enter with the access code (123), and then press         to enter.
- Use the keys        and        to access the desired function.
- After selecting the function, press         (short touch) to display the  configured value for that function.
- Use the keys        and        to change the value and then press         to record the new value and return 
to the functions menu.
- To return to the normal operation, press         until            appear.

5. FUCTIONS WITH FACILITATED ACCESS

Registers of minimum and maximum temperatures 

Press     . The minimum registered temperature appears and after soon the maximum registered 
temperature.

Nota: 

To reset the registers, keep the key     pressed during the visualization of the minimum and 

maximum temperatures until            to be showed.            

SET

SET

SET

SET

SET

If the instrument is configured as alarm, set the F09 and F10 act points normally and ignore 

ST2

 and 

F11. If the temperature goes out the specified range and ring the alarm, press        and         to inhibit the 
sound

.

6. SIGNALING

ST1

-

 

1st stage output on

ST2

-

 

2nd stage output on

- Detached sensor or temperature outside the specified range

With F08=4 the ST2 output is activated when the temperature reaches a value equal 

ST1

 minus the 

configurated value in F09 (

ST1

-F09), or when the temperature reaches a value equal 

ST1

 plus the 

configurated value in F10 (

ST1

+F10)

Ex. :

- Temperature in ST1 = 25 ºC

- Value in F08 = 4 

- Value in F09 = 2

- Value in F10 = 5

The 

ST2

 output will be kept on when the temperature is below 23 ºC (25-2) or above 30 ºC (25+5). If 

ST1 

value is changed to 24 ºC the alarm values will be automatically modified to 22 and 29 ºC.
IF the functions F14 and F15 are set with zero, the 

ST2

 output will be kepped on while the alarm 

condition persist.

SET

enso

S

r

Power 

supply

Load 1

CO

M

M

ON

 

Loads

supply

ST

(N

O)

ST

(N

O)

1

2

3

4

5

6

7

8

9

10 11 12

115 V

(12 V)

230 V

(24 V)

0

72 mm

29

 m

m

7. WIRING DIAGRAM

7 - 8
7 - 9

115V
230V  

12V
24V

MT-518Ri

MT-518RiL

Load 2

- Refrigerator
- Heating
- Contactor
- Solenoid

- Refrigerator
- Heating
- Contactor
- Solenoid

Load 1

Load 2

Above specified current use contactors.

Dimension of the clipping for

setting of the instrument

IMPORTANT

For more information contact our application eng. department through e-mail 

support@ fullgauge.com

 or dial +55 51 3475.3308.

According to the chapters of norm IEC 60364:  

1:

 Install protector against overvoltage on the power supply

2:

 Sensor cables and signal cables of the computer may be joined, but not in the same electric conduit 

through which the electric input and the activation of the loads run

3:

 Install transient suppresors (RC filters) parallel to the loads as to increase the product life of the 

relays.

Contact suppresor connection diagram

S

up

pr

es

or

A1

A2

A1 e A2 are the
contactor coils.

Diagram for suppresor installation

for direct drive load inputs

Load

S

up

pr

es

or

For direct activation the maximum
specified current should be taken
into consideration.

Note:

 The user can increase the length of the sensor cable to up to 200 meters, by using PP 2 X 24 AWG 

cable. For immersion in water, use thermometric well. 

PROTECTIVE VINYL:

This adhesive vinyl (included inside the packing) protects the instruments against 
water drippings, as in commercial refrigerators, for example.
Do the application after finishing the electrical connections.

Remove the protective paper 
and apply the vinyl on the entire 
superior part of the device, 
folding the flaps as indicated by 
the arrows.