Ver.08 

MT-512Ri LOG

DIGITAL CONTROLLER FOR COOLING WITH 

NATURAL DEFROST THROUGH COMPRESSOR

 SHUTDOWN AND INTERNAL DATALOGGER

1. DESCRIPTION

The 

MT-512Ri LOG

 is a temperature controller and indicator, with a joined cyclical timer. Controls 

cooling and defrost through compressor shutdowns. It also has an internal datalogger and a serial 

®

output for communication with the SITRAD .
Product complies with NSF (United States).

2. APPLICATIONS

• Counters
• Cooled chambers

3. TECHNICAL SPECIFICATION

- Power supply:

MT-512Ri LOG     115 or 230 Vac ±10%(50/60 Hz)
MT-512RiL  LOG     12 or 24 Vac/dc

- Control temperature:

 -50 to 75.0ºC / -58 to 167°F

- Load current:

NO    16(8)A/250Vac  1HP 
NC     8A/250Vac    

- Dimensions: 

71 x 28 x 71mm

4. CONFIGURATIONS

4.1 - control temperature adjust (SETPOINT)

- Press          for 2 seconds until appears            and then release the key. 
 The set control temperature will appear.
- Use the         and         keys in order to change the value and, when ready, press          to record.

4.2 - To enter the function menu

Press        and,        at the same time for 2 seconds until           appears, letting off on it instantly. When
          appears, press        (short touch) and enter the code (123) through the keys       and       to confirm 
press the key         . Through the keys        and        access the other functions and do the same to adjust 
them. To leave the menu and return to normal operation, press         (Long touch) until            appears.

4.3 - Functions

Entry of access code
Advanced configuration functions
Adjustment of clock and date 

- Operating temperature:  

0 to 50 ºC / 32 to 122°F

- Operating humidity: 

10 to 90% RH (without condensation)

SET

SET

SET

SET

SET

4.4 - Parameters table

Description

Fun

Datalogger operation mode

Indication offset  

Minimum setpoint allowed for the end user

Maximum setpoint allowed for the end user 

Control differential (hysteresis)

Delay to turn the cooling output on

Cooling time 

 

Defrosting time

Initial state up on energizing the instrument

Indication of the temperature locked during defrost

Delay on the activation of the instrument

Additional time at the end of the first cycle

Datalogger sampling interval

Variation of the temperature to force data recording

Variation of the output to force data recording

Memory overwriting?

Address of the instrument on the network RS-485 

(defrosts interval)

Min

Max

Unit

Default

0

-5.0 / -9

-50 / -58

-50 / -58

0.1 / 1

0

1

0

0 - cooling

0 - no

0

0

1

0 / 0

0

0 - no

001

2

5.0 / 9

75.0 / 167

75.0 / 167

20.0 / 40

999

999

999

1 - defrost

1 - yes

240

240

999

10.0 / 17

1

1 - yes

247

-

°C / °F

°C / °F

°C / °F

°C / °F

sec.

min.

 min.

-

-

min.

min.

sec

°C / °F

-

-

-

0 / 0

-50.0 / -58

75.0 / 167

1.0 / 2

20

240

30

0 - cooling

0 - no

0

0

30

0 / 0

0

1 - yes

1

5. PARAMETERS DESCRIPTION

Datalogger operation mode

This indicates how the data storage device operates:

Always OFF
Always ON
Manual operation

Offset indication

Allows it to compensate for eventual temperature misreading, usually due to a sensor replacement.

 Minimum setpoint allowed to the end user 

Electronic limit whose purpose is prevent that too low setpoint temperatures are regulated.

Maximum setpoint allowed to the end user

Electronic limit whose purpose is prevent that too high setpoint temperatures are regulated.

Control differential (hysteresis)

It is the difference of temperature (hysteresis) between to turn OFF and turn ON the refrigeration output.

 

Delay to turn the cooling output on

cooling output

Cooling time 

Defrosting time

Initial state up on energizing the instrumen

Indication of the temperature locked during defrost

It is the minimum time that 

 will keep on, it means, space of time between the last drive and 

the next stop.

(defrosts interval)

It is the time which compressor will turn on and turn off only by sensor temperature. After passed this 
time, the controller will enter in defrost mode.

It is the minimum time that the cooling output will keep off to make natural defrost. After passed this time, 
the controller will enter in cooling mode.

Indicates what mode the controller will work when turned on :

Cooling
Defrost

This function prevents the visualization of temperature elevation during defrost, maintaining the last 
temperature indication prior to defrost. At the beginning of the refrigeration cycle, a normal temperature 
indication will again take place after fan delay.

No
Yes

When the instrument is powered on, its control is kept disabled during a time, delaying the start of process. 
During this time, it works only as temperature indicator. 

Complement time at the first  refrigeration  cycle to certify that the first defrost cycle do not be started very 
early.

temperature and the cooling outputs status.

Indicates whether the change in the cooling output will force the recording of data in memory regardless 
of the time of sampling set in F13:

Delay on the activation of the instrument

Additional time at the end of the first cycle

Datalogger sampling interval

Time period in which the controller will register a sample of the 

Variation of the temperature to force data recording

Temperature difference to forces the recording of data in the memory, independently of the sampling time 
configured at F13. To desable this function, just decrease the value until the  message            appears in 
the display.

Variation of the output to force data recording

6. FUNCTIONS WITH FACILITATED ACCESS

6.1 - Maximum and minimum temperature logs

Press the         key. The minimum and maximum temperatures registered will appear. 

Note:

 To restart the logs you just have to keep the       key pressed during the viewing of the minimum 

and maximum temperatures until             to be displayed.             

OFF

ON

Memory overwriting?

This allows you to start overwriting data from datalogger memory beginning when the memory is full. 
This prevents the latest data recorded from equipment being erased first.

No
Yes

Address of the instrument on the network RS-485 

®

This is the device address for communication with 

Sitrad

 software. Note: You cannot have two or more 

devices with the same address in the network. 

6.3 - Clearing datalogger memory:

Press the        and         keys for 4 seconds to display                    . The display shows           . If you 
don't want to clear the memory press        . To clear the memory press       until          is displayed and 
press           to confirm and exit the function.

SET

SET

SET

6.2 - 

ou can turn the internal 

recording

 ON or OFF by pressing      

   

for

 seconds  The            message is displayed followed by the message           (datalogger           ) 

and          (datalogger         ). If the parameter F15 is configured with the values          or           the 
messages            or             will be displayed accordingly.

Manual datalogger activation

Y

 

temperature data 

 (datalogger)

        or     

 10

MT512LOGV08-05T

-1

1

157

COMPONENT