Full Gauge Controls Microsol RST Advanced Скачать руководство пользователя страница 1

MCSOLADV

ANRST02-01T

-17099

1. DESCRIPTION

The 

Microsol

 

RST Advanced   

is  a  digital  thermostat  with  control  logic  for 

heating or cooling. The unit is equipped with a clock, events schedule for rational and 
economical use of the controlled load, and protected access to configuration parameters. 
It features the Holiday function which saves on power consumption during periods when 
the system is idle. 
The 

Microsol

 

Advanced

  line  is  characterized  by  its  unique  design  for  use  in 

residential environments, by the easiness of operation with keys for easy access to the 
controller's main resources and by the use of the custom display. The display technology 
employed allows presenting in a complete and simple manner the solar heating system's 
information, such as: output status, thermostat operation mode, sensor temperature and 
time.

2. APPLICATION

- Heating systems for thermal reservoirs
- Floor heating
- Air conditioning

3. TECHNICAL SPECIFICATIONS

- Power:

 

Microsol

 

RST Advanced

-10%(50/60Hz) or version 115Vac 

+-10%(50/60Hz)

- Operation temperature:

 0 to 40ºC

- Operation humidity: 

10 to 90% UR (without condensation)

- Sensors: 

The

 

Microsol

 

RST Advanced

 

 

has 1 sensor:

Sensor T1:

 Thermostat - SB41 Sensor, plastic tip, 2m

- Control temperature:

 

Sensor T1:

 -50 to 105ºC / -58 to 221ºF

- Resolution: 

0.1ºC between -10 and 100ºC and 1ºC in the remainder of the range 

1ºF in all of the range

- Control output:

 The

 

Microsol

 

RST Advanced

  has one relay output

:

 

         

AUX

 - Relay output, max. 16A, resistance

3500W in 220Vca (1750W in 127 Vca)

- Dimensions: 

104 x 148 x 32 mm

- Display:

 LCD 2.75'' with backlight

5. OPERATIONS FOR DOMESTIC USER
5.1 KEY MAP

The controller has easy-access to user resources. Contains table with description of the 
following:

Short key press: set the thermostat temperature

Long touch (4 seconds): access to advanced settings

Long touch (see F10 parameter): enables/disables function block

Short key press: access the menu to set the events schedule

Short touch: switches way thermostat mode (AUT / MAN)

Long key press (4 seconds): enables/disables thermostat Holiday mode (OFF)

Short touch: accesses hour and day settings menu

DIGITAL THERMOSTAT 

WITH EVENTS SCHEDULE

Ver. 02

SET

SET

RST 

 

Advanced

4. INDICATIONS AND SCREEN

4.1 PRESENTATION

1

2

3

4

5

6

7

8

9

10

11

Schedule key

Thermostat mode key

Clock key

Lowering key

Set key

Increasing key

Indication of the thermostat operation mode

Controller signals

Representation of the solar heating system

Lower display numbers

Upper display numbers

4.2 INDICATIONS

SET

LOC

5.2 THERMOSTAT TEMPERATURE

Sets the operating temperature of the thermostat. 
To adjust this parameter, short press the 

SET 

button. Use the     and     keys to 

adjust the value. To confirm, short press the 

SET

 button and the value will be 

saved in the controller memory. This parameter can be adjusted between the 
values  defined  in  the  advanced  configuration  for  parameters: 

[,F03]

  – 

Minimum value of the thermostat temperature and 

[,F04]

 – Maximum value 

of the thermostat temperature.

5.3 THERMOSTAT OPERATING MODE

With  each  short  press  of  the        button  you  can  change  the  operating  mode  of  the 
thermostat output between AUT and MAN modes.

                                             
                                                        

                                                

Note:

 When adjusting the thermostat mode, the controller changes into the new mode 5 

seconds after your selection. This is also the time required for the parameter to be stored in 
its memory.
Manual mode is used when you wish to control the load outside the hours set in the events 
schedule.
In manual mode, the thermostat output is still associated to the sensor temperature via the 
thermostat heating temperature (

[TEMP]

 parameter). In this mode, the controller allows 

the output to be turned on during the period programmed in the parameter 

[,F05]

.

AUX

AUT

AUX

MAN

SET

 AUT = Thermostat in automatic mode, operating 
according  to  the  configuration  of  the  events 
schedule and sensor temperature.

MAN = Thermostat in manual mode. It remains in 
this mode for the time set in 

[,F05]

- thermostat 

manual  override  time,  and  returns  to AUT  mode 
after this time has elapsed.

5.3.1 VACATION MODE

To enable/disable the Vacation mode, the     key must be held for 4 seconds.
                                         
                                                  

OFF: vacation mode enabled.

When enabled: 
The  event  schedule  is  ignored,  the  support  outlet  is  turned  off,  resulting  in  energy 
consumption reduction.

Obs.:

 In thermostat mode settings, the controller takes on the new mode 5 seconds after 

its selection. This also is the time necessary for the parameter to be stored in its memory.

4 seconds

off

AUX

A

SET

1

2

3

6

5

4

AUX

am pm

SET LOC

AUX

AUT

off

MAN

am pm

7

11

8

9

10


A

A

A

am

pm

AUX

In programming, cleared parameter setting
In programming, blocked parameter setting
Fahrenheit scale temperature Indication
Celsius scale temperature Indication
Thermostat output on, if F01=Cool
Thermostat output on, if F01=Heat
Indicates the occurrence of a controller error
Function block setting
Before noon (standard clock 12pm)
After noon (standard clock 12pm)

RST

AUX

AUX

AUT

Отзывы: