DIGITAL CONTROLLER FOR HEATING OR COOLING
WITH DEFROST AND CONFIGURABLE
ALARM OUTPUT
MT514EV03-02T
-18524
4. INDICATIONS AND KEYS
5.
INSTALLATION - ASSEMBLING AND ELECTRICAL CONNECTIONS
1. DESCRIPTION
The
MT-514
e
is a temperature controller for cooling or heating applications. It has an internal
audible alarm (buzzer) and an output for alarm control that can also be configured for electric defrost,
hot gas defrost, fan or as a second compressor that will act in parallel with the main one. The minimum
and maximum temperature record is displayed at the touch of a single key
;
(Flatec). Another
available feature is the shutdown of control functions, making it possible for the
MT-514
e
to
operate only as a temperature indicator. And through an intelligent function blocking system, it prevents
unauthorized persons from changing the control parameters.
Product is compliant with UL Inc. (United States and Canada).
2. APPLICATION
• Vaccine refrigerators
• Refrigerated counters
• Freezer rooms
• Hot counters
evolution
MT-514
e
V
er
.03
1
5 6 7 8
2 3 4
9
POWER
SUPPLY
SENSOR
10 11 12 13 14 15 16 17
REFR
HEAT
R
E
FR
115 Vac
1
5 6 7 8
2 3 4
9
POWER
SUPPLY
SENSOR
10 11 12 13 14 15 16 17
230 Vac
C
O
M
M
O
N
1
5 6 7 8
2 3 4
9
POWER
SUPPLY
SENSOR
10 11 12 13 14 15 16 17
1
5 6 7 8
2 3 4
9
POWER
SUPPLY
SENSOR
10 11 12 13 14 15 16 17
12 Vac/dc
24 Vac/dc
D1
D1
V
E
N
T/
C
O
M
P
A
U
X
V
E
N
T/
C
O
M
P
A
U
X
V
E
N
T/
C
O
M
P
A
U
X
V
E
N
T/
C
O
M
P
A
U
X
A
LA
R
M
/
D
E
FR
A
LA
R
M
/
D
E
FR
A
LA
R
M
/
D
E
FR
A
LA
R
M
/
D
E
FR
C
O
M
M
O
N
NO
NC
REFR
HEAT
NO
NC
C
O
M
M
O
N
C
O
M
M
O
N
6. OPERATIONS
6.1.
Quick Access Menu Map
To access or browse in the quick access menu, use the
;
key (quick touch) while the temperature is
being displayed by the controller. Each touch displays the next function of the list; for confirming, use
the
/
key (quick touch). For further details, refer to chapter 6.3.
REFR
HEAT
NO
NC
REFR
HEAT
NO
NC
C
O
M
M
O
N
C
O
M
M
O
N
C
O
M
M
O
N
C
O
M
M
O
N
D1
D1
MT-514
e
MT-514
e
R
E
FR
R
E
FR
R
E
F
R
3. TECHNICAL SPECIFICATIONS
6.2.
Quick access keys map
When controller is on temperature display mode, the following keys can be used as a shortcut for the
following functions:
Hold down for 2 seconds: setpoint adjustment.
Quick touch: displayof current process and sensor temperature when
[F41]
= 1 or 2.
/
<
<
<
Hold down for 2 seconds: inhibit audible alarm (buzzer).
E251415
COMPONENT
Have this manual in the palm of
your hand by
FG Finder
application.
;
*Blinking led (when
[F26]
= 7): Indicates that OUT1 has been activated and the compressor delay is ocurring before
trigger OUT2
Control functions
shutdown
Function
blocking
Serial
Programming
Protection
level
Defrost
IP 65
FRONT
Audible
Alarm
WARNING
ACCESSORIES:
Only use original Full Gauge Controls accessories.
If you have any questions, please contact technical support.
AUTHORIZED SERVICE:
The installation or maintenance of the product must be performed by qualified professionals only;
DUE TO YOUR CONSTANT EVOLUTION, THE FULL GAUGE CONTROLS RESERVES THE RIGHT TO
CHANGE THE INFORMATION CONTAINED IN THIS MANUAL AT ANY TIME WITHOUT NOTICE.
BEFORE INSTALLING THE CONTROLLER, WE RECOMMEND READING THROUGH THE
ENTIRE INSTRUCTION MANUAL IN ORDER TO AVOID POSSIBLE DAMAGE TO THE
PRODUCT.
PRECAUTIONS WHEN INSTALLING THE PRODUCT:
Before performing any procedure on this instrument, disconnect it from the mains;
Ensure that the instrument has adequate ventilation and avoid installation in panels containing
devices that may cause it to operate outside the specified temperature limits;
Install the product away from sources that may generate electromagnetic disturbances such as:
motors, contactors, relays, solenoid valves, etc;
Control temperature
-50 to 105ºC (-58 to 221°F)*
Power supply
MT-514 E:
115 or 230 Vac ±10%(50/60 Hz)
MT-514 EL:
12 or 24 Vac/dc +10%
Operating temperature
0 to 50 ºC / 32 to 122°F
Operating humidity
10 to 90%RH (without condensation)
Dimensions (WxHxD)
76 x 34 x 77 mm
Load current (outputs)
OUT1:
16(12)A 250Vac 2HP
OUT2:
10A / 240Vac 1/4HP
Dimensions of the clipping for fixing
of the instrument
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
(*)
This instrument measures and controls temperatures of up to 200°C/392°F, using the silicone sensor cable SB59
(sold separately).
Note:
The sensor cable lenght can be increased by the user up to 200 meters using PP 2 x 24 AWG cable.
MT-514
e
Set key
Quick Access
Menu Key (Flatec)
Functions lock indication LED
Temperature unit indication LED
Increase key
Decrease key
Alarm indication LED
Cooling indication LED
Heating indication LED
Defrost indication LED
Panel (Front View)
Panel
(Side View)
Dimension of the clipping
for fixing of the
instrument in panel
71
mm
± 0,5
29
mm
± 0,5
FOR INSTALLATIONS WHERE A SEALING IS REQUIRED
TO AVOID LIQUID CONTACT, THE CUT FOR THE
CONTROLLER MUST BE OF 70,5X29mm MAXIMUM. THE
SIDE LOCKS MUST BE FIXED SO IT PRESSES THE
RUBBER SEALING AVOIDING INFILTRATION BETWEEN
THE CUT AND THE CONTROLLER.
ATTENTION
Connection
115 Vac
Loads supply
Loads supply
Loads supply
Loads supply
Connection
230 Vac
Connection
12 Vac/dc
Connection
24 Vac/dc
IMPORTANT
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE
SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER
TERMINALS;
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID
DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:
;
;
MT-514
e
MT-514
e
;
DEFROST (ON/OFF)
;
FUNCTIONS LOCKDOWN
;
CONTROL FUNCTIONS
(ON/OFF)
ADJUSTING DESIRED
TEMPERATURE
(SETPOINT)
EXIT FUNCTION
;
FUNCTION SELECTION
;
VISUALIZATION OF
PROCESSES
;
ERASE MIN. AND MAX.
VALUES
MT-514
e
MT-514
e
MT-514
e
MT-514
e
MT-514
e
MT-514
e
MIN. AND MAX.
TEMPERATURE RECORD
;
MT-514
e
Quick touch: maximum and minimum temperature display.
Pressed for 5 seconds: turn on/turn off the control functions.