Full Gauge Controls AHC-80 plus Скачать руководство пользователя страница 1

PSYCHROMETRIC CONTROLLER

 OF AIR RELATIVE HUMIDITY

 AND TEMPERATURE

AHC-80 plus

Ver.01

1. DESCRIPTION

The

 AHC-80 plus

 is a psychrometric controller that has two totally configurable stages. It is designed 

to control the relative humidity of the air and temperature for the: acclimatization of stocking of fruits and 
flowers, air conditioning, textile industry, laboratories, operating rooms, concrete durability trials, wood 
drying, among other applications.
The measurement is made using the temperature difference between a dry bulb and a wet bulb. It is a 
psychrometric, acknowledged as a precise and stable method for determining the relative humidity of 
the air.
This controller is very user friendly, and offers the user a great deal of ease in adjusting the configuration 
parameters.

2. TECHNICAL SPECIFICATION

- Power supply: 

115/230Vac (50/60Hz)

- Control temperature: 

-5.0 to 50.0°C (±0.1°C)

- Control humidity:

 40 to 100%RH (±1%RH)

- Operating temperature: 

0 to 50 ºC

- Operating humidity: 

10 to 90%RH (without condensation)

- Maximum current per output: 

8(3) A / 250Vac 1/4HP

- Dimensions: 

71 x 28 x 71mm

3. CONFIGURATION

3.1 - Temperature and huimidity control (SETPOINTS)

- Press         for two seconds until the following figure appears           .
- If the function          has a value of 0 or 1                 will appear as well as with the values of the
adjusted temperature and humidity. 
- If the function                 has a value of 2 or 3                               will appear as well as with the value of the
adjusted humidity.
- Use the keys        and         to modify the values, and when ready, press          to confirm.

3.2 - Parameters alteration (advanced functions)

- Acess the advanced functions by pressing simultaneously the keys       and       for 2 seconds until 
appears            , releasing after that. Soon appears            , so press         (short touch). 
- Use the keys        and        to enter the acess code (123), when ready press         .
- Use the keys        and        to acess the desired function.
- After select the function, press         (short touch) to visualize the value configured for that function.
- Use the keys       and       to change the value and, when ready, press         to save the configured value 
and return to functions menu.
- To return the normal operation, press         (long touch) until            appears.

SET

SET

SET

SET

SET

SET

SET

Description

 

Minimum

Maximum

 

Unit

Access code (123)

Atmospheric pressure

Operating mode for the 1st stage

Minimum setpoint allowed for the 1st stage

Maximum setpoint allowed for the 1st stage

Control differential (hysteresis) for the 1st stage

Delay for restart of the output for the 1st stage

Operating mode for the 2nd stage

Minimum setpoint allowed for the 2nd stage

Maximum setpoint allowed for the 2nd stage

Control differential (hysteresis) for the 2nd stage

Delay for restart of the output for the 2nd stage

Cyclical timer for the 2nd stage - time on

Cyclical timer for the 2nd stage - time off

Preferential indication

Address of the instrument on the network RS-485

-

mmHg

°C (%RH)

°C (%RH)

°C (%RH)

sec.

 

%RH

%RH

%RH

sec.

sec.

sec.

-

-

-99

400

(*)

-5.0 (1.0)

-5.0 (1.0)

0.1 (1.0)

 0

(**)

1.0 

 

1.0

1.0

0

0

(***)

001

999

800

(*)

50.0 (100)

50.0 (100)

20.0

999

(**)

 

100

100

20.0

999

999

999

(***)

247

3.3 - Advanced functions

Fun

(**) Operating mode for the 2nd stage

           Dehumidification
           Humidification

(***)Preferential indication

           Temperature / humidity
           Only temperature
           Only humidity

(*) Operating mode for the 1st stage

           Refrigeration
           Heating
           Dehumidification
           Humidification

4. STANDARDIZATION (LOCAL CALIBRATION)

 Recommended execution when:
- the probe is substituted;
- the length of the sensor cable is altered.
In these cases, small deviations may arise when measuring temperatures, which may be compensated. 
For this purpose, proceed in the following manner:
- Place the probe fully into a bucket of water that is a temperature similar to that of the chamber;
- Keep this water moving, and monitor the temperature using a good quality thermometer (reference).

- Wait a few minutes for the temperatures of the dry bulb and the wet bulb to stabilize and equalize to the 
temperature indicated by the reference thermometer, pursuant to what is described below:
- Simultaneously press        and        for ten seconds until            appears.
-Releasing  the  keys,  the  temperature  will  appear  to  be  adjusted,  according  to  the  reference 
thermometer.
- Use the keys        and        to adjust the value an, when ready, press         to memorize the new value.

REMARKS 1

 The length of the sensors cable may be increased by the user itself, using a PP 2x24 AWG 

cable, additionally supplied by Full Gauge Controls upon request.
Substitute the cordon that covers the humid bulb by another one double cordon made of white cotton, 
when necessary.

REMARKS  2:

  In  order  to  obtain  a  reliable  humidity  indication,  wait  at  least  20  minutes  for  the 

temperatures to stabilize, then reinstall the probe.

5. VISUALIZATION OF THE TEMPERATURE OF THE WET BULB

To visualize the temperature of the wet bulb, all you have to do is touch the key         .
The message            will appear, and then the temperature measured by the wet bulb.

SET

SET

6. MAXIMUM AND MINIMUM LOGS

Press          . The  display  will  indicate              followed  by  the  maximum  and  minimum  temperatures
registered.  Then  the            will  appear,  followed  by  the  minimum  and  maximum  humidity  levels 
registered.

Note: 

To restart the records you just have to keep the           key pressed during the viewing of the

minimum and maximum temperatures until            is displayed.

7. VISUALIZATION OF THE OTHER VARIABLE

If the function         is configured to only visualize the temperature or only visualize the humidity, you
may visualize the other variable through a simple touch of the key        .

8. INSTALLATION OF THE PROBE FOR THE 

AHC-80 plus

1. Attach the stainless steel reservoir through the 2 holes. (fig. 01)
2. Fill the plastic recipient with water. (fig. 02)
3. Place the plastic recipient in the stainless steel 
reservoir, as indicated in the figure.(fig. 03)

(fig. 01)

(fig. 02)

(fig. 03)

4. Leave the silicon hose (disconnected from the probe) with it pointing down, let the water run until you 
notice bubbles of air rising in the plastic recipient.  This process will guarantee that there is no air inside 
the hose.
5. Slowly lift the end of the silicon hose (fig. 04), using the upper level of the water in the hose to 
determine the level inside the reservoir. Using chalk, mark this level on the wall..
6. Use the mark made on the wall to position the probe (fig. 05) so that the stainless steel part (fig. 06) of 
the probe has its middle positioned to the center of the mark. Guaranteeing that through communication 
vessels, there is water up to half of the stainless steel part, and so we have the humid covering in the 
liquid.
7.Connect the silicon hose to the probe. Take care that the covering is in contact with the water, and that 
there is plenty of water in the plastic recipient.

(fig. 04)

(fig. 05)

(fig. 06)

9. MESSAGES AND SIGNS

           Sensor for the dry bulb is disconnected or is not in operating range
           Sensor for the wet bulb is disconnected or is not in operating range
           Excessive difference in temperature between the dry and wet bulbs
           Temperature of the wet bulb is higher than the dry bulb

Atmospheric pressure (in mmHg):

The formula for calculating the atmospheric pressure based on the altitude is:
P (mmHg)   0,00000446171 x   -  0,091019 x  +  759,787

2

@

where x = altitude (in meters)

ST1

AHC-80 plus 

ST2

Obs: 

The tube can not suffer

alterations in the cut.

AHC80PL1-09T