3 .4 .5
Additional charge
The charge in the outdoor units corresponds to the maximum distances between the outdoor unit and the hydraulic
unit defined in
. If the distances are greater, an additional charge of R410A is required. The additional
charge depends on the distance between the outdoor unit and the hydraulic unit for each type of appliance.
The additional charge of R410A must necessarily be made by an approved refrigeration engineer.
e 5, 6, 8
(Outdoor unit WOYA060LFCA, WOYA080LFCA)
15m < Length of the connections ≤ 30m
(Length of the connections - 15m) x 25 g/m= g
Models /
Factory charge
Length of the
connections m
16
17
X
29
30
e 5, 6 /
1100 g
Charge g
1125
1150
1100 + (X - 15) x 25 = g
1450
1475
e 8 /
1400 g
1425
1450
1400 + (X - 15) x 25 = g
1750
1775
e
(Outdoor unit WOYA100LFTA)
15m < Length of the connections ≤ 30m
(Length of the connections - 15m) x 40 g/m= g
Model /
Factory charge
Length of the
connections m
16
17
X
29
30
e 10 /
1800 g
Charge g
1840
1880
1800 + (X - 15) x 40 = g
2360
2400
e 13, 16
(Outdoor unit WOYG112LHT, WOYG112LCTA, WOYG140LCTA)
15m < Length of the connections ≤ 20m
(Length of the connections - 15) x 50 = g
Model /
Factory charge
Length of the
connections m
16
17
18
19
20
e 13 / 16
2500 g
Charge g
2550
2600
2650
2700
2750
R410A
figure 23 - "Gas" bottle R410A
Liquid
Gas
- The charge must be introduced after creating the
vacuum and before the hydraulic unit is filled with gas,
as follows :
- Disconnect the vacuum pump (yellow hose) and connect a
bottle of R410A
instead in the fluid extraction position
- Open the bottle’s valve.
- Bleed the yellow hose by loosening it slightly on the
Manifold
side.
- Place the bottle on scales with a minimum accuracy of
10g. Note the weight.
- Carefully open the blue valve slightly and check the
value shown on the scales.
- As soon as the value displayed has dropped by the
value for the calculated additional charge, close the
bottle and disconnect it.
- Then rapidly disconnect the hose connected to the appliance.
- Proceed to fill the hydraulic unit with gas.
"
Warning
•
Only use R410A !
•
Only use tools suitable for R410A (set of manometers).
•
Always charge in the fluid phase.
•
Never exceed the length or the maximum difference in level.
Installation and operation manual "1764 - EN"
- 27 -
Air to Water Heat Pump, split system
Comfort 5,6
Comfort 8
Comfort 10
Comfort 5, 6, 8
(Outdoor unit WOYA060LFCA, WOYA080LFCA)
Comfort 10
(Outdoor unit WOYA100LFTA)
Содержание WOYA060LFCA
Страница 23: ... Installation and operation manual 1764 EN 23 Air to Water Heat Pump split system ...
Страница 29: ... Installation and operation manual 1764 EN 29 Air to Water Heat Pump split system ...
Страница 33: ...Installation and operation manual 1764 EN 33 Air to Water Heat Pump split system ...
Страница 35: ... Installation and operation manual 1764 EN 35 Air to Water Heat Pump split system ...
Страница 71: ...Installation and operation manual 1764 EN 71 Air to Water Heat Pump split system ...
Страница 73: ... Installation and operation manual 1764 EN 73 Air to Water Heat Pump split system ...
Страница 79: ... Installation and operation manual 1764 EN 79 Air to Water Heat Pump split system ...
Страница 86: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 86 ...
Страница 87: ...Installation and operation manual 1764 EN 87 Air to Water Heat Pump split system ...
Страница 88: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 88 ...
Страница 89: ...Installation and operation manual 1764 EN 89 Air to Water Heat Pump split system ...
Страница 90: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 90 ...
Страница 91: ... Installation and operation manual 1764 EN 91 Air to Water Heat Pump split system ...