1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown in the table below. However,
the maximum rotation number is limited in the range shown in the figure below based on the in-
door fan mode and the outdoor temperature.
•
Rotation number range of compressor
Model name
Minimum rotation number
Maximum rotation number
RSG07KPCE
RSG09KPCE
10 rps
84 rps
RSG12KPCE
10 rps
90 rps
1-1. Cooling operation
- (04-1) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ROG07KPCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EJ_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 12 16 SR_CH02_AS059EJ_01 ...
Страница 31: ...3 TROUBLESHOOTING 2021 12 16 SR_CH03_AS059EJ_01 ...
Страница 34: ......
Страница 91: ...4 CONTROL AND FUNCTIONS 2021 12 16 SR_CH04_AS059EJ_01 ...
Страница 123: ...5 FILED WORKING 2021 12 16 SR_CH05_AS059EJ_01 ...