2-16. E: 95. Compressor motor control error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
9 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 95
Detective actuator
Outdoor unit
Main PCB
1. When running the compressor, if the detected rotor
location is out of phase with actual rotor location
more than 90°, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Main PCB failure
Compressor failure
Check point 1. Check Noise from Compressor
Turn on Power and check operation noise.
→ If an abnormal noise show, replace compres-
sor.
↓
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
↓
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
↓
End
2-16. E: 95. Compressor motor control error (Outdoor unit)
- (03-22) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ROG07KPCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EJ_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 12 16 SR_CH02_AS059EJ_01 ...
Страница 31: ...3 TROUBLESHOOTING 2021 12 16 SR_CH03_AS059EJ_01 ...
Страница 34: ......
Страница 91: ...4 CONTROL AND FUNCTIONS 2021 12 16 SR_CH04_AS059EJ_01 ...
Страница 123: ...5 FILED WORKING 2021 12 16 SR_CH05_AS059EJ_01 ...