2-5. E: 41. Room temperature sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 41
Detective actuator
Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-13.
(07-12 models: CN1)
If the voltage does not appear, replace main PCB.
↓
End
2-5. E: 41. Room temperature sensor error (Indoor unit)
- (03-10) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ROG07KPCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EJ_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 12 16 SR_CH02_AS059EJ_01 ...
Страница 31: ...3 TROUBLESHOOTING 2021 12 16 SR_CH03_AS059EJ_01 ...
Страница 34: ......
Страница 91: ...4 CONTROL AND FUNCTIONS 2021 12 16 SR_CH04_AS059EJ_01 ...
Страница 123: ...5 FILED WORKING 2021 12 16 SR_CH05_AS059EJ_01 ...