TX2560 M2 / RX2560 M2
Upgrade and Maintenance Manual
437
Front panel and external connectors
Ê
"Removing the system air duct" on page 91
Ê
"Removing the system fan holder" on page 93
13.1.2 Removing the front panel module
Removing front panel cables from the system board
Figure 322: Disconnecting the front panel cables
Ê
Disconnect the front panel cable from the system board (1).
Ê
If applicable, disconnect the front VGA cable from the system board (2).
Ê
Disconnect the front USB cable from the system board (3).
Ê
Remove all front panel cables from the cable guide (A).
Removing the front panel module
I
Unlocking and securing the front panel is illustrated by the example of the
rack server. In case of tower servers, the accessible drive locking bar is
located on the top of the drive bay. Further information see section
"Opening the accessible drive locking bar" on page 100
A
Содержание PRIMERGY RX2560 M2
Страница 6: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 ...
Страница 26: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Contents ...
Страница 42: ...42 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Before you start ...
Страница 110: ...110 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Basic hardware procedures ...
Страница 152: ...152 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Power supply unit PSU ...
Страница 282: ...282 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Hard disk drive HDD solid state drive SSD ...
Страница 364: ...364 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Main memory ...
Страница 434: ...434 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Accessible drives ...
Страница 492: ...492 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 System board and components ...
Страница 508: ...508 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Converting a tower model to a rack model ...
Страница 544: ...544 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Cabling ...
Страница 568: ...568 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Appendix ...