PSU configurations
PSU 2
PSU 1
Figure 42: PSU bays
AC PSU
Input
Output
80 PLUS Platinum
100 V - 127 V
200 V - 240 V
1000 W
1600 W
Assembly rules
–
Always install a dummy cover into an unused PSU bay to comply with
applicable EMC regulations and satisfy cooling requirements.
–
For a redundant power supply configuration you need always two PSUs with
the same power class.
Mixed assembly of PSUs from different power classes (e.g. class 1 or class
2) within a system is not supported.
–
Mixing of Platinum PSUs within same class and different manufacturer (e.g.
class 1) within a system is supported.
6.3
Redundant power supply
6.3.1
Installing a hot-plug PSU
Customer Replaceable
Unit (CRU)
Hardware: 5 minutes
Tools:
tool-less
Power supply unit (PSU)
76
Upgrade and Maintenance Manual
RX2450 M1