PRIMEQUEST 2000 Series Design Guide
3.5.3 Guidelines for Selecting a 200V Power Distribution Box
AC200V Power Distribution Box Brief Specifications
Guidelines on the Number of AC200V Power Distribution Boxes
Copyright 2016-2017 FUJITSU LIMITED
U number Voltage
Input
Output
Output current
1U
200V
NEMA L6-30P
IEC320 C19
3
24A/BOX
16A per box
0U
200V
NEMA L6-30P
IEC320 C19
3
24A/BOX
16A per box
Model
200V non-redundant
configuration
200V redundant
configuration
200V dual power feed
configuration
2400E2/2400E3
1
1
2
2400E2/2400E3 with
Memory Scale-up Board
1
2
2
2800E2/2800E3
2
2
4
2800E2/2800E3,
2800B2/2800B3
(*1) (4,500VA or less)
1
2
2
(*1) Calculate the required number of power distribution boxes according to the maximum apparent power. The maximum
apparent power can be calculated by using the Power Calculator ("Tool").
As the above example shows, if the maximum apparent power is 4.500VA or less , the number of power distribution boxes can
be reduced.