3-2. Outdoor fan control
¢
Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢
Fan speed
Models: AOHG07KPCA and AOHG09KPCA
Fan speed is defined by outdoor temperature and rotation number of the compressor.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
19
°C
10
°C
0
°C
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry at low outdoor temp.
Y zone
Y zone
Z zone
F zone
G zone
S-HIGH2
—
930
—
—
—
—
S-HIGH1
950
930
—
—
—
—
HIGH
950
930
—
—
—
—
10
—
690
—
—
—
—
9
950
690
950
950
950
950
8
780
690
780
780
270
250
7
780
690
780
780
270
250
6
780
690
780
540
270
200
5
780
690
780
360
240
170
4
780
550
780
270
210
170
3
680
510
680
270
190
170
2
610
480
610
270
190
170
1
580
480
580
270
170
170
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
rotation number of compressor.
Fan speed after defrost control: 930 rpm
3-2. Outdoor fan control
- (04-12) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...