2-17. E: 77. Heat sink thermistor error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
7 time flash
Timer indicator
7 time flash
Economy indicator
Continuous flash
Error code
E: 77
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Heat sink temperature thermistor
Heat sink temperature thermistor short or open detected
Forecast of cause
Connector failure
Thermistor failure
Inverter PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the Heat sink thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of inverter PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-14.
If the voltage does not appear, replace inverter PCB.
↓
End
2-17. E: 77. Heat sink thermistor error (Outdoor unit)
- (03-22) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General AOHH30KMTB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Страница 36: ......
Страница 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Страница 94: ......
Страница 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...