3-3. Setting of external input and output
•
Indoor unit
Input
Connection point
Function setting number 46
Function
CN46
00
Operation/Stop mode 1 (R.C. enabled)
01
(Setting prohibited)
02
Forced stop mode
03
Operation/Stop mode 2 (R.C. disabled)
Output
Connection point
Function setting number 60
Function
CN47
00
Operation status
01 to 08
(Setting prohibited)
09
Error status
10
Indoor unit fan operation status
11
(Setting prohibited)
•
External Input and Output PCB
Switch setting
Input
Output
Rotary
switch
SW302
CN313
CN314
CN310
CN311
CN312
1
Edge
Operation/Stop
Not available
Operation
status
Error status
Indoor unit fan
status
Pulse
Operation
Stop
2
Edge*
Forced
thermostat off
Not available
Error status
Indoor unit fan
operation
status
Not available
3 to 9, A
(Setting prohibited)
B
Forced
thermostat off
Not available
Operation
status
Indoor unit fan
operation
status
Not available
C
Forced
thermostat off
Not available
Operation
status
Error status
Not available
D
Forced
thermostat off
Not available
Operation
status
Indoor unit fan
operation
status
Error status
NOTES:
• When the rotary switch is selected to “1”, the operation of the connector input of the indoor
unit and the External Input and Output PCB input are the same. The operation content de-
pends on the setting of function setting number 46.
• *: The external input other than “Operation/Stop” is available only when the SW302 is set to
“Edge”.
3-3. Setting of external input and output
- (05-18) -
3. External input and output (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание General AOHH30KMTB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Страница 36: ......
Страница 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Страница 94: ......
Страница 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...