7-13. Human sensor for energy saving
If no one enters the room for approximately 20 minutes, the set temperature is automatically con-
trolled. (When someone comes back into the room, the human sensor detect this, and automatically
revert to the original settings.)
Operation mode
Operation details
(If there is no one in the room for a while)
Cool/Dry
The setting temperature is increased by maximum 2°C.
(Maximum setting temperature: 30°C)
Heat
The setting temperature is decreased by maximum 4°C.
(Minimum setting temperature: 16°C)
Auto
Energy saving function is performed automatically for the selected mode
(cool/heat/dry).
• Application range:
Vertical angle 90
°
Side view
Horizontal angle 100
°
Top view
90
°
7 m
50
°
50
°
7 m
Energy saving function may not work when the room temperature is very different from the tem-
perature defined in the temperature setting, such as when immediately after starting the operation.
• Details about detection with the human sensor:
The human sensor detects whether there are people in the room by looking for movement by peo-
ple in the room.
7-14. Peak cut operation
The current value is limited to reduce the power consumption by external input.
Peak cut level
Level 1
Level 2
Level 3
Level 4
Peak cut for rated capacity
Forced thermostat
off
50%
75%
100%
NOTES:
• During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-13. Human sensor for energy saving
- (04-26) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHH30KMTB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Страница 36: ......
Страница 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Страница 94: ......
Страница 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...