![Fujitsu General AOHH30KMTB Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/fujitsu/general-aohh30kmtb/general-aohh30kmtb_service-manual_2343870119.webp)
7-9. External electrical heater control
The external electrical heater is operated as below.
When the room
temperature rises
When the room
temperature drops
Ts: Setting temperature
Heater : Off
Heater : On
Heater : Off
Ts -10
°
C
Ts -1
°
C
Ts -3
°
C
Ts -12
°
C
NOTES:
• When the compressor stop, external electric heater is off.
• It operates only in heating mode and when the indoor fan operates. (However, S-LOW is exclud-
ed.)
7-10. Electronic expansion valve control
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the table below.
Operation mode
Pulse range
Cooling/dry mode
Between 47 and 480 pulses
Heating mode
Between 39 and 480 pulses
NOTE:
At the time of supplying the power to the outdoor unit, the initialization of the electronic ex-
pansion valve is operated (528 pulses are input to the closing direction).
7-11. Prevention to restart for 3 minutes (3 minutes st)
When the compressor fails to start for the number of times below, it does not enter operation status
for 3 minutes.
Retry number
10
Retry set number
3
When the compressor fails to start in the retry set number above, the compressor is stopped.
7-12. 4-way valve control
• If heating mode is selected at the compressor start, 4-way valve is energized for heating.
• When the air conditioner is switched between cooling and heating mode, compressor is stopped,
and the 4-way valve is switched when the 3 minutes passes and the compressor is started.
7-9. External electrical heater control
- (04-25) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHH30KMTB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Страница 36: ......
Страница 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Страница 94: ......
Страница 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...