2-8. E: 53. Drain pump error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 53
Detective actuator
Indoor unit main PCB
When Float switch is ON for more than 3 minutes.
Float switch
Forecast of cause
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
Check point 1. Check float switch
•
Check operation of float switch. (any blocking by dust, etc.)
•
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
↓
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
↓
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
↓
Check point 4. Replace drain pump
If check point 1 to 3 do not improve the symptom, replace drain pump.
↓
Check point 5. Replace main PCB
If check point 4 do not improve the symptom, replace main PCB.
↓
End
2-8. E: 53. Drain pump error (Indoor unit)
- (03-14) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...