
2-4. E: 23. Combination error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 23
Detective actuator
Indoor unit
The outdoor unit receives the serial signal of applied
refrigerant information from indoor unit.
Forecast of cause
Incorrect indoor unit is selected.
Check point 1. Check the type of indoor unit
•
Check the type of the connected indoor unit.
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANAL”.
↓
Check point 2. Replace the main PCB
If check point 1 do not improve the symptom, replace the main PCB of the outdoor unit.
↓
End
2-4. E: 23. Combination error (Outdoor unit)
- (03-10) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...