FUJITSU Storage ETERNUS DX60 S2 Disk storage system User’s Guide -Installation-
45
Copyright 2014 FUJITSU LIMITED
P3AM-5502-05ENZ0
Chapter 3
Rack Installation
This chapter describes the procedure for installing the ETERNUS DX Disk storage system in a
rack.
Make sure to check "Safety Precautions" before installing the ETERNUS DX Disk storage
system in a rack. Also refer to the manual provided with racks.
CAUTION
Do
•
When performing the installation, make sure to wear a wrist strap or
touch a metal part to discharge the human body's natural static
electricity. Failure to discharge static electricity may cause device
failure.
•
If components are installed in a way other as described in this
section, damage and/or device failure or electrical shock may occur.
•
Do not install the ETERNUS DX Disk storage system with cables,
such as power cords, connected.
•
The ETERNUS DX Disk storage system contains delicate
components, and should be handled gently. Do not drop or knock the
ETERNUS DX Disk storage system against the rack when installing
it. Also, do not knock the other devices installed in the rack.
•
The center of gravity must be taken into consideration to prevent a
rack from toppling over. Enclosures should generally be installed
from bottom to top to lower the center of gravity and to ensure the
safe use of racks.
•
If the storage system is installed at the bottom of a rack, a space for the
surplus of cables may not be available in some racks, preventing the
storage system from being pulled out when maintenance work is
required. In this case, secure a space of 1U or more at the bottom when
installing the storage system.
•
To install an enclosure, power distribution units, power synchronized
units, and UPS units in a single rack, mount the devices in the following
order (from bottom to top).
Table 3.1
Device installation order
Order
Device
1
UPS
2
Power distribution unit, Power synchronized unit
3
Controller enclosure
4
Drive enclosure