Power Supply Connection
Connect the power cords (AC cables) of the ETERNUS DX to the power sockets, the UPS sockets, or the power
control unit sockets.
For details about the types and the number of power sockets that can be used, refer to "Power Socket Specifica-
tions" in "Site Planning Guide".
Input Power Supply Lines
For details on input power supply lines, refer to "Site Planning Guide".
UPS Connection
It is recommended that an Uninterruptible Power Supply System (UPS) is used as the power supply source for the
ETERNUS DX to cope with power outages and momentary voltage drops in the normal power supply.
When one of the power supply lines fails for redundantly configured UPS units with two power supply lines, all of
the power for the ETERNUS DX must be supplied from the other line. Select a UPS that can supply sufficient pow-
er so that the total value of the power requirements does not exceed the UPS output capacity in case only one
power supply line is available.
For details about the necessary UPS output capacity, refer to the specifications of the UPS that is used.
A UPS must satisfy the following conditions:
●
Rating Capacity
Secure a sufficient rating capacity for the total value of the maximum power requirements for the enclosures
that are to be installed.
To find the maximum power level requirements for each enclosure, refer to "Installation Specifications" in "Site
Planning Guide".
●
Supply Time
The total time for the server to shut down and for the ETERNUS DX to power off must be taken into consideration
for the power supply time of the battery.
●
Switching Time during Power Failure
The normal power supply must be switched to UPS output within 15ms after a power failure occurs.
●
Socket Type
If the power plug type and the socket type of the UPS do not match, it is necessary to equip the UPS (AC output)
with an appropriate type of socket. Request a qualified electrician to perform the necessary work to make termi-
nal block connections available.
●
Power Supply Configuration
If a UPS is used, make sure that it supplies power to all the enclosures.
Configurations where the controller enclosure is powered by the UPS while the drive enclosures are powered di-
rectly from AC are not supported.
4. Connection Configuration
Power Supply Connection
162
FUJITSU Storage ETERNUS DX500 S4/DX600 S4, ETERNUS DX500 S3/DX600 S3 Hybrid Storage Systems Design Guide (Basic)
Copyright 2019 FUJITSU LIMITED
P3AM-7722-25ENZ0
Содержание ETERNUS DX500 S3/DX600 S3
Страница 218: ......