•
When connecting three or more servers
Figure 98
Power Supply Control Using a Power Synchronized Unit (When Connecting Three or More
Servers)
ETERNUS DX
PWC
Power synchronized
unit#0
UPS unit for
Server#0
PWC
PWC
ETERNUS DX
PWC
Server#2
AC sensor
unit#1
Server#3
Server#0
UPS unit for
Server#1
Server#1
UPS unit for
Server#2
UPS unit for
Server#3
AC sensor
unit#0
Turns on: 1
Turns off: 2
Turns on: 2
Turns off: 1
4
4
3
Powering on sequence
1
Power on of all the server UPS units
2
Server startup
The server OS startup is suspended until the ETERNUS DX startup is complete (*1).
3
Instruction from the power synchronized unit to turn on the ETERNUS DX
4
ETERNUS DX startup
*1:
The server must be set to suspend server OS startup until the ETERNUS DX startup is complete.
Powering off sequence
1
Shutdown of all the servers
2
Shutdown of all the server UPS units
3
Instruction from the power synchronized unit to turn off the ETERNUS DX
4
ETERNUS DX shutdown
5. Connection Configuration
Power Synchronized Connections
201
Design Guide
Содержание ETERNUS DX S5 Series
Страница 335: ......