8-4. Details of function
¢
Control input function
When function setting is "Operation/Stop" mode 1
• In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-00
-
Input of indoor unit
Terminal
Off → On
Operation
On → Off
Stop
60-00 / 1
External input and
output PCB
Input 1
Off → On
Operation
On → Off
Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
• In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-00
60-00 / 1
External input and
output PCB
Input 1
Pulse
Operation
Input 2
Pulse
Stop
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.