1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG36KQTA
A zone
55 rps
B zone
52 rps
C zone
47 rps
D zone
39 rps
E zone
33 rps
F zone
25 rps
G zone
18 rps
H zone
20 rps
I zone
20 rps
J zone
21 rps
K zone
24 rps
AOYG45KQTA
A zone
60 rps
B zone
57 rps
C zone
48 rps
D zone
36 rps
E zone
27 rps
F zone
24 rps
G zone
20 rps
H zone
20 rps
I zone
20 rps
J zone
26 rps
K zone
30 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-7) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG36KRLB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Страница 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Страница 50: ......
Страница 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Страница 120: ......
Страница 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...