8-4. Indoor unit fan motor over temperature protection
When satisfy the following conditions, the protection works.
• After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
• IPM trip protection works.
• Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
•
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
– Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
– Fan stop 40 seconds when IPM trip protection works.
– Fan stop 50 seconds when corrent overload protection works.
8-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition
108°C
Release condition
80°C
(3 minutes after compressor stop)
8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
8-7. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Cooling/Dry
Heating
Trigger condition
-20°C
Release condition
-15°C
8-4. Indoor unit fan motor over temperature protection
- (04-35) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...