8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Models: AOYG30KATA and AOYG36KATA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
8.0 A
7.5 A
50°C ≤ Ta < 52°C
12.0 A
11.5 A
42°C ≤ Ta < 50°C
14.0 A
13.5 A
2°C ≤ Ta < 42°C
18.0 A
17.5 A
Ta < 2°C
20.0 A
19.5 A
Heating
2°C ≤ Ta
18.0 A
17.5 A
Ta < 2°C
20.0 A
19.5 A
¢
Model: AOYG45KATA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
10.0 A
9.5 A
50°C ≤ Ta < 52°C
13.0 A
12.5 A
46°C ≤ Ta < 50°C
15.0 A
14.5 A
42°C ≤ Ta < 46°C
18.0 A
17.5 A
2°C ≤ Ta < 42°C
20.0 A
19.5 A
Ta < 2°C
24.0 A
23.5 A
Heating
2°C ≤ Ta
20.0 A
19.5 A
Ta < 2°C
24.0 A
23.5 A
¢
Model: AOYG54KATA
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
10.0 A
9.5 A
50°C ≤ Ta < 52°C
13.0 A
12.5 A
46°C ≤ Ta < 50°C
15.0 A
14.5 A
42°C ≤ Ta < 46°C
18.0 A
17.5 A
2°C ≤ Ta < 42°C
20.0 A
19.5 A
Ta < 2°C
24.0 A
23.5 A
Heating
12°C ≤ Ta
20.0 A
19.5 A
2°C ≤ Ta < 12°C
21.0 A
20.5 A
Ta < 2°C
24.0 A
23.5 A
8-3. Current release control
- (04-34) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...