![Fujitsu AUXG30KRLB Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/fujitsu/auxg30krlb/auxg30krlb_service-instruction_2343789017.webp)
3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢
Fan speed
Indoor fan speed is defined as below.
Operation mode
Fan mode
Speed (rpm)
AUXG30KRLB
AUXG36KRLB
AUXG45KRLB
AUXG54KRLB
Heating
HIGH
570
640
670
690
MED+
530
600
630
680
MED
510
560
590
630
LOW
470
510
530
570
QUIET
420
430
470
480
Cool air
prevention
300
300
300
300
S-LOW
270
270
270
270
Cooling/Fan
HIGH
570
640
670
690
MED
510
560
590
630
LOW
470
510
530
570
QUIET
420
430
470
480
Soft quiet
300*
1
300*
1
300*
1
300*
1
S-LOW
270*
2
270*
2
270*
2
270*
2
Dry
X zone: 420
J zone: 420
X zone: 430
J zone: 430
X zone: 470
J zone: 470
X zone: 480
J zone: 480
*1: Fan mode only
*2: Cooling mode only
¢
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
¢
Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2
°C
HIGH mode
MED mode
LOW mode
2
°C
> Tr - Ts ≥ 1
°C
1
°C > Tr - Ts
Tr - Ts ≥ 2.5
°C
2.5
°C
> Tr - Ts ≥ 1.5
°C
1.5
°C > Tr - Ts
3-1. Indoor fan control
- (04-12) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...