![Fujitsu AUXG18KVLA Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/fujitsu/auxg18kvla/auxg18kvla_service-manual_2343781156.webp)
2. Auto changeover operation
When the air conditioner is set to AUTO mode by remote controller, operation starts in the optimum
mode from among heating, cooling, dry and monitoring modes. During operation, the optimum mode
is automatically switched in accordance with temperature changes. The temperature can be set be-
tween 18°C and 30°C in 1.0°C steps.
• When operation starts, indoor fan and outdoor fan are operated for around 1 minute.
Room temperature and outdoor temperature are sensed, and the operation mode is selected in
accordance with the table below.
Room temperature
Operation mode
Tr > Ts + 2°C
Cooling
Ts + 2°C ≥ Tr ≥ Ts - 2°C
Middle zone
Tr < Ts - 2°C
Heating
Tr: Room temperature
Ts: Setting temperature
NOTE:
When the operation mode is middle zone, indoor unit operation mode is selected as below.
• Same operation mode is selected as outdoor unit.
If outdoor unit is operating in cooling and heating mode, indoor unit will be operated by
the same operation mode.
• Selected by outdoor temperature.
If outdoor unit is operating in other than cooling and heating mode, indoor unit will be op-
erated according to the outdoor temperature as below.
Outdoor temp.
Operation mode
25°C or more
Cooling
Less than 25°C
Heating
• When the compressor was stopped for 6 consecutive minutes by temperature control function af-
ter the cooling or heating mode was selected as above, operation is switched to monitoring mode
and the operation mode selection is done again.
• When the middle zone is selected on the predetermining of the operation mode, the operation
mode before the changing to the monitoring mode is selected.
- (04-10) -
2. Auto changeover operation
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG18KVLA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Страница 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Страница 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Страница 72: ......
Страница 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Страница 146: ......
Страница 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...