5. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
5-1. Models: AOU9RLFC and AOU12RLFC
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5
7.5
10
15
20
ft
16
24
32
49
65
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.877
0.874
10
32
—
—
0.956
0.891
0.888
7.5
24
—
0.988
0.960
0.895
0.892
5
16
1.017
0.992
0.964
0.899
0.895
0
0
1.025
1.000
0.971
0.906
0.902
Indoor unit is lower than outdoor
unit *2
-5
-16
1.025
1.000
0.971
0.906
0.902
-7.5
-24
—
1.000
0.971
0.906
0.902
-10
-32
—
—
0.971
0.906
0.902
-15
-49
—
—
—
0.906
0.902
HEATING
Pipe length
m
5
7.5
10
15
20
ft
16
24
32
49
65
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.933
0.925
10
32
—
—
0.981
0.933
0.925
7.5
24
—
1.000
0.981
0.933
0.925
5
16
1.017
1.000
0.981
0.933
0.925
0
0
1.017
1.000
0.981
0.933
0.925
Indoor unit is lower than outdoor
unit *2
-5
-16
1.012
0.995
0.976
0.928
0.920
-7.5
-24
—
0.993
0.974
0.926
0.918
-10
-32
—
—
0.971
0.923
0.916
-15
-49
—
—
—
0.914
0.906
- 53 -
5-1. Models: AOU9RLFC and AOU12RLFC
5. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU9-18RLFC
OUTDOOR UNIT
AOU9-18RLFC