- 52 -
O
U
T
D
OOR UNIT
AOY
G
30, 36
LMTA
2-1. Installation space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
•
When the upper space is open:
•
When there is an obstruction in the upper space:
Unit: mm
When there are obstacles at the rear only.
When there are obstacles at the rear and sides.
When there are obstacles at the front only.
When there are obstacles at the front and rear.
Unit: mm
When there are obstacles at the rear and
above.
When there are obstacles at the rear, sides, and
above.
100 or more
250 or more
300 or more
100 or more
600 or more
600 or more
100 or more
300 or more
Max. 500
600 or more
1,000 or more
100 or more
250 or more
500 or more
Max. 500