1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
•
Compressor frequency range
Model name
Minimum frequency
Maximum frequency
ASYG09KHCA
ASYG12KHCA
8 rps
74 rps
ASYG14KHCA
8 rps
74 rps
1-1. Cooling operation
- (04-1) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOYG09KHCAN
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 01 27 SR_CH01_AS032EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 27 SR_CH02_AS032EF_01 ...
Страница 35: ...3 TROUBLESHOOTING 2020 03 19 SR_CH03_AS032EF_01 ...
Страница 82: ...5 2 Outdoor unit 03 46 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 83: ...4 CONTROL AND FUNCTIONS 2020 04 07 SR_CH04_AS032EF_01 ...
Страница 117: ...5 FILED WORKING 2020 04 07 SR_CH05_AS032EF_01 ...