8. Various protections
8-1. Discharge gas temperature over-rise prevention control
The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis-
charge gas temperature.
• When the discharge temperature becomes higher than the trigger condition, the compressor fre-
quency is decreased as the table below, and it continues to decrease until the discharge tempera-
ture becomes lower than the trigger condition.
• When the discharge temperature becomes lower than the release condition, control of compressor
frequency is released.
• When the discharge temperature becomes higher than the compressor protection temperature,
the compressor is stopped and the indoor unit LED starts blinking.
Trigger condition
104°C
Compressor frequency
-20 rps/120 seconds
Release condition
101°C
Compressor protection temperature
110°C
8-2. Anti-freezing control (cooling and dry mode)
The compressor frequency is decrease in cooling and dry mode when the indoor unit heat exchang-
er temperature sensor detects the temperature lower than the trigger condition.
When the indoor unit heat exchanger temperature reaches release condition, the anti-freezing con-
trol is stopped.
Trigger condition
39.2°F (4°C)
Release condition
Outdoor temp. ≥ 50°F (10°C)*
1
Outdoor temp. ≥ 53.6°F (12°C)*
2
44.6°F (7°C)
Outdoor temp. < 50°F (10°C)*
1
Outdoor temp. < 53.6°F (12°C)*
2
55.4°F (13°C)
*1: During the outdoor temperature dropping
*2: During the outdoor temperature rising
8-1. Discharge gas temperature over-rise prevention control
- (04-29) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LZAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Страница 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Страница 36: ......
Страница 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Страница 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...