1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
14.0°F
(-10°C)
32.0°F
(0°C)
50.0°F
(10°C)
66.2°F
(19°C)
100.4°F
(38°C)
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOUG09LZAS1
AOUG12LZAS1
A zone
37 rps
B zone
37 rps
C zone
37 rps
D zone
28 rps
E zone
1 rps
F zone
22 rps
AOUG15LZAS1
A zone
33 rps
B zone
33 rps
C zone
33 rps
D zone
25 rps
E zone
10 rps
F zone
20 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-5) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS