1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
•
Compressor frequency range
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUG09LZAS
ASUG12LZAS
ASUG15LZAS
8
130
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
A zone
B zone
57.2°F
(14°C)
C zone
14.0°F
(-10°C)
Outdoor
temperature rises
Outdoor
temperature drops
53.6°F
(12°C)
10.4°F
(
-12
°C)
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASUG09LZAS
ASUG12LZAS
A zone
130
130
58
46
B zone
130
130
58
46
C zone
130
130
58
46
ASUG15LZAS
A zone
130
130
54
42
B zone
130
130
54
42
C zone
130
130
54
42
1-2. Heating operation
- (04-3) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LZAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Страница 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Страница 36: ......
Страница 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Страница 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...