1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• →hen the room temperature is within the range of +6.0 °C to -1.0 °C of the setting temperature,
the rotation number of compressor is controlled within the range shown in the table below. Howev-
er, the maximum rotation number is limited in the range shown in the figure below based on the
indoor fan mode and the outdoor temperature.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASHG07KGTE
12
62
ASHG09KGTE
12
67
ASHG12KGTE
ASHG14KGTE
12
83
1-1. Cooling operation
- (04-1) -
1. Rotation number control of compressor
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание AOHG07KGCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Страница 36: ......
Страница 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Страница 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Страница 92: ......
Страница 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...