2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 11
Detective actuator Indoor unit
Main PCB
→hen the outdoor unit cannot receive the serial signal
from indoor unit more than 10seconds.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Indoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
If there is an abnormal condition, correct it by referring to the installation manual or the
DESIGN
& TECHNICAL MANUAL
.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 207 V (AC 230 V -10%) to AC 253 V (AC 230 V +10%) appears at
outdoor unit terminal L—N.
+
-
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- (03-5) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание AOHG07KGCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Страница 36: ......
Страница 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Страница 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Страница 92: ......
Страница 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...