![Fujitsu AOHG07KGCA Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/fujitsu/aohg07kgca/aohg07kgca_service-manual_2344036119.webp)
7-6. POWERFUL operation
The PO→ERFUL operation starts by pressing PO→ERFUL button on the remote controller.
The indoor unit and outdoor unit operate at maximum power as shown in the table below.
Compressor frequency
Maximum
Fan mode
PO→ERFUL
Vertical airflow direction
louver setting
Cooling
3
Dry
Heating
6
Release condition:
• Cooling/Dry
Room temperature ≤ Setting temperature -0.5°C or Operation time has passed 20 minutes.
• Heating
Room temperature ≥ Setting tempe0.5°C or Operation time has passed 20 minutes.
7-7. Fresh air control
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.
Operation
Stop
Operation
Stop
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
7-8. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
•
Triggering condition
– 30 minutes after compressor stopped.
– Outdoor unit heat exchanger temperature (Tn)
-4°C
Off
On
Tn
Tn
-2°C
→hen the jumper wire (JM2) is disconnected:
5°C
Off
On
Tn
Tn
7°C
7-6. PO→ERFUL operation
- (04-27) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание AOHG07KGCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 3 11 SR_CH01_AS069EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 3 11 SR_CH02_AS069EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS069EG_01 ...
Страница 36: ......
Страница 89: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS069EG_01 ...
Страница 91: ...8 6 High temperature and high pressure release control heating mode 04 32 CONTENTS continued ...
Страница 92: ......
Страница 125: ...5 FILED WORKING 2022 03 25 SR_CH05_AS069EG_01 ...