DESIGN & TECHNICAL MANUAL

INDOOR

OUTDOOR

AOGA25FBTAH

AOGA18FBTAH

ARGA18FMTA

ARGA25FMTA

AIR CONDITIONER

Duct type 

Содержание AOGA18FBTAH

Страница 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOGA25FBTAH AOGA18FBTAH ARGA18FMTA ARGA25FMTA AIR CONDITIONER Duct type ...

Страница 2: ...1 INDOOR UNIT DTR_AR087E_02 2015 02 05 DUCT TYPE ARGA18FMTA ARGA25FMTA ...

Страница 3: ...MAL MODE 01 11 7 2 STATIC PRESSURE MODE 1 01 13 7 3 STATIC PRESSURE MODE 2 01 15 7 4 STATIC PRESSURE MODE 3 01 17 8 OPERATION NOISE SOUND PRESSURE 01 19 8 1 NOISE LEVEL CURVE 01 19 8 2 SOUND LEVEL CHECK POINT 01 20 9 SAFETY DEVICES 01 21 10 EXTERNAL INPUT OUTPUT 01 22 10 1 EXTERNAL INPUT 01 22 10 2 EXTERNAL OUTPUT 01 23 11 FUNCTION SETTINGS 01 25 11 1 INDOOR UNIT 01 25 11 2 INDOOR UNIT Setting by ...

Страница 4: ... from the width with the flanking control box embedded inside the chassis Easy maintenance z z The fan and motor is easily accessible by the divided panel structure Structural improvement is attained by making the bottom panel in two pieces front and rear The internal fan casing is also manufactured in two pieces namely upper and lower The maintenance of the motor and fan can be easily carried out...

Страница 5: ...operation z z Quiet operation at 25 dB A is possible in quiet mode Economy operation z z The power consumption can be reduced Operation in high ambient temp z z The operation is secured under the ambient temperature of up to 52 degrees celsius Cooling 21 to 52 C ...

Страница 6: ...t Weekly timer Set back timer setup Easy to understand operation z z Variable timer control The operation display sections are zoned according to time and operation enabling variable programming to match application Simple installation z z Components are compatible with standard switch boxes Flat back construction allows equipment to be installed wherever it is needed European switch box JIS box S...

Страница 7: ...Set the current time 7 DAY DAY OFF button Temporarily cancels of one day timer 8 SET BACK button Pressed to select the set back timer 9 Set time button Pressed to set time 10 TIMER DELETE button The schedule of a weekly timer is deleted 11 TIMER SET button Sets the date hour minute and on off time 12 Vertical airflow direction and swing button Push for two seconds to change the swing mode 13 Horiz...

Страница 8: ...Available voltage range 198 to 264 V COOLING T1 condition Capacity kW 5 20 5 20 6 45 6 45 Btu h 17 800 17 800 22 000 22 000 Input power kW 1 51 1 53 1 88 1 91 Current A 7 0 6 5 8 8 8 5 EER Btu hW 11 79 11 63 11 70 11 52 Sensible capacity kW 4 10 4 10 5 08 5 08 Power factor 98 1 98 1 97 1 93 6 Moisture removal l h pints h 1 6 2 8 1 9 3 3 Maximum operating current 1 Cooling A 13 5 16 7 Fan Airflow r...

Страница 9: ...NS 444 MODEL ARGA18FMTA ARGA25FMTA Unit mm Refrigerant piping flare connection Gas Refrigerant piping flare connection Liquid Drain piping connection Drain piping connection with cap Knock out hole for fresh air Front view Top view Side view L Side view R Rear view ...

Страница 10: ...RGA18 25FMTA INSTALLATION PLACE Unit mm MAINTENANCE HOLE WHEN USING A SQUARE DUCT BOTTOM AIR INTAKE HOLE It shall be possible to install and remove the control box It shall be possible to install and remove the control box fan units and filter ...

Страница 11: ... 01 08 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA WIRING DIAGRAMS 555 MODEL ARGA18FMTA ...

Страница 12: ... 01 09 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA MODEL ARGA25FMTA ...

Страница 13: ...4 2 07 5 52 4 10 2 09 45 3 57 3 09 2 11 3 98 3 11 2 15 4 12 3 38 2 15 4 39 3 39 2 18 4 59 3 66 2 19 4 79 3 65 2 21 5 07 3 88 2 23 52 3 06 2 86 2 33 3 41 2 87 2 37 3 52 3 13 2 38 3 76 3 13 2 40 3 87 3 39 2 42 4 11 3 37 2 44 4 34 3 59 2 46 AFR 20 0 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP ...

Страница 14: ... 297 292 264 CFM 677 659 630 618 559 Med m3 h 860 795 l s 239 221 CFM 506 468 Low m3 h 820 740 690 l s 228 206 192 CFM 483 436 406 Quiet m3 h 740 600 l s 206 167 CFM 436 353 Hi Med Low Quiet Q h Characteristic curve Static pressure Pa 50 40 30 20 10 0 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 ...

Страница 15: ...3 h 980 910 830 l s 272 254 231 CFM 577 539 489 Low m3 h 825 690 l s 229 192 CFM 486 406 Quiet m3 h 630 525 l s 175 146 CFM 371 309 Hi Med Low Quiet Q h Characteristic curve Static pressure Pa 50 40 30 20 10 0 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Capacity ...

Страница 16: ...264 CFM 677 559 Med m3 h 995 810 l s 276 225 CFM 586 477 Low m3 h 805 685 l s 224 190 CFM 474 403 Quiet m3 h 645 550 l s 181 153 CFM 383 324 Q h Characteristic curve Static pressure Pa 70 60 50 40 30 20 10 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h 104 102 100 98 96 94 92 Capacity ...

Страница 17: ... Med m3 h 1000 815 l s 278 226 CFM 589 480 Low m3 h 830 680 l s 231 189 CFM 489 400 Quiet m3 h 650 540 l s 181 150 CFM 383 318 Q h Characteristic curve Static pressure Pa 70 60 50 40 30 20 10 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h 104 102 100 98 96 94 92 Capacity ...

Страница 18: ...CFM 668 559 Med m3 h 990 825 l s 275 229 CFM 583 486 Low m3 h 820 710 l s 228 197 CFM 483 418 Quiet m3 h 685 585 l s 190 163 CFM 403 344 Q h Characteristic curve Static pressure Pa 110 100 90 80 70 60 50 40 30 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Capacity ...

Страница 19: ... m3 h 1020 800 l s 283 222 CFM 600 471 Low m3 h 835 670 l s 232 186 CFM 491 394 Quiet m3 h 660 530 l s 183 147 CFM 388 312 Q h Characteristic curve Static pressure Pa 110 100 90 80 70 60 50 40 30 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Capacity ...

Страница 20: ... 671 618 Med m3 h 1030 920 l s 286 256 CFM 606 542 Low m3 h 880 790 l s 244 219 CFM 518 465 Quiet m3 h 710 650 l s 197 181 CFM 418 383 Q h Characteristic curve Static pressure Pa 150 140 130 120 110 100 90 80 70 60 50 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Capacity ...

Страница 21: ... h 1000 810 l s 278 225 CFM 589 477 Low m3 h 840 680 l s 233 189 CFM 494 400 Quiet m3 h 660 525 l s 183 146 CFM 388 309 Q h Characteristic curve Static pressure Pa 150 140 130 120 110 100 90 80 70 60 50 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Cooling z z Cooling capacity 104 102 100 98 96 94 92 500 600 700 800 900 1 000 1 100 1 200 1 300 Airflow m3 h Capacity ...

Страница 22: ...e level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 MODEL ARGA25FMTA HIGH QUIET COOLING z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50...

Страница 23: ... 01 20 DUCT TYPE ARGA18 25FMTA DUCT TYPE ARGA18 25FMTA SOUND LEVEL CHECK POINT 88888 Microphone Measuring duct Measuring duct Set the static pressure as rating in this area 2 m 1 m 1 5 m AIR Microphone ...

Страница 24: ...RGA18 25FMTA DUCT TYPE ARGA18 25FMTA SAFETY DEVICES 999 Protection form Models ARGA18FMTA ARGA25FMTA Circuit protection Current fuse PC board 250 V 3 15 A Fan motor protection Thermal protection OFF 135 15 C ON 115 15 C ...

Страница 25: ...flow mode AUTO Mode at previous operation Air direction swing Standard air direction swing OFF Air direction at previous operation Circuit diagram example z z Indoor unit control PC board Connected unit Ex Switch Connector 1 3 Signal Locally purchased Make the distance from the PC board to the connected unit within 10 m Contact capacity DC 24 V or more 10 mA or more Please use non polar relays and...

Страница 26: ...example z z Locally purchased Ex Display Indoor control PC board Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector Make the distance from the PC board to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA 10 m DC 24 V ON OFF Operation Stop Indoor unit Output signal Parts Optional z z Model name UTD ECS5A Wire External output ...

Страница 27: ...control operation Circuit diagram example z z Locally purchased Indoor control PC board Connector 1 12 V on off 2 Signal Relay power supply Make the distance from the PC board to the connected unit within 10 m Relay spec Rated DC 12 V 50 mA or less Ex Fan Connected unit Ex Relay unit 10 m ON OFF Operation Stop Indoor fan Output signal Parts Optional z z Model name UTD ECS5A Wire Fresh air output ...

Страница 28: ...g table The DIP switches are normally set to make the unit number 00 Factory setting Unit number DIP switch No 1 2 3 4 00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON INDOOR UN...

Страница 29: ...TION Turn on the power Before turning on the power of the indoor units make sure the piping air tight test and vacuuming have been conducted Also check again to make sure no wiring mistakes were made before turning on the power FUNCTION SETTING METHOD for Wired remote controller Setting method z z 1 Press the SET TEMP buttons and FAN button simultaneously for more than 5 seconds to enter the funct...

Страница 30: ...ttings may be selected between the following two Function Number or Setting Value Settings will not be changed if inenable numbers or setting values are selected 1 Filter sign 2 Static pressure 3 Room temperature sensor control for cooling 4 Auto restart 5 Room temperature sensor switching 6 External input control 7 Room temperature sensor switching Aux 1 Filter sign Select appropriate intervals f...

Страница 31: ...Number Setting Value Setting Description 42 00 Indoor unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller 6 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Function Number Setting Value Setting Description 46 ...

Страница 32: ...prohibited SW2 Setting change prohibited SW3 Setting change prohibited SW4 Setting change prohibited SW5 Setting change prohibited SW6 Memory backup setting Do not use DIP Switch 2 SWITCH POSITION Wired remote controller z z 1 2 3 4 5 6 Front case back side DIP Switch 2 All switches fixed at OFF DIP Switch 1 ON ON OFF ...

Страница 33: ...TCH 1 SETTING SW6 setting z z Memory backup setting Set to ON to use batteries for the memory backup If batteries are not used all of settings stored in memory will be deleted if there is a power failure u Factory setting SW6 Memory backup u OFF Disable ON Enable ...

Страница 34: ...ted Round flange is also used when the fresh air duct is installed Round flange UTD RF204 507mm Long life filter UTD LF25NA Long life filter can be mounted to the indoor unit Remote sensor UTY XSZX New amenity space can be offered by installing the Remote sensor in the remote controller External control set UTD ECS5A Use to connect with various peripheral devices and air conditioner PC board ...

Страница 35: ...DTR_AO202E_01 2015 01 19 SINGLE TYPE AOGA18FBTAH AOGA25FBTAH 2 OUTDOOR UNIT ...

Страница 36: ...IGERANT CIRCUIT 02 04 4 WIRING DIAGRAMS 02 06 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 08 6 ADDITIONAL CHARGE CALCULATION 02 10 7 AIRFLOW 02 11 8 OPERATION NOISE SOUND PRESSURE 02 12 8 1 NOISE LEVEL CURVE 02 12 8 2 SOUND LEVEL CHECK POINT 02 13 9 ELECTRIC CHARACTERISTICS 02 14 10 SAFETY DEVICES 02 15 ...

Страница 37: ...Available voltage range 198 to 264 V Starting current A 42 55 Fan Airflow rate m3 h 3 200 3 300 Type Q ty Propeller 1 Motor output W 75 59 Sound pressure level Cooling dB A 54 54 Heat exchanger type Dimensions H W D mm 630 x 901 x 36 4 798 900 36 4 Fin pitch 1 45 1 30 Rows x Stages 2 30 2 38 Pipe type Copper Fin type Surface treatment Aluminium Blue fin Compressor Type Q ty Rotary 1 Motor output W...

Страница 38: ...s larger than stated the condition will be the same as those without any obstacles Height above the floor level should be 50 mm or more When there are obstacles at the back and front sides When there are obstacles at the back side s and top When there are obstacles at the back side with the installation of more than one unit 600 or more 300 or more 300 or more 300 or more 600 1000 300 or more 300 ...

Страница 39: ...re than one unit When there are obstacles at the back and front sides 600 or more 250 or more 250 or more 300 or more 600 1000 100 or more 300 or more 100 300 250 or more Service space If the space is larger than stated the condition will be the same as those without any obstacles Height above the floor level should be 50 mm or more Air flow 900 650 830 370 99 196 21 9 77 31 330 400 170 147 12 Top...

Страница 40: ... 02 04 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH REFRIGERANT CIRCUIT 333 MODEL AOGA18FBTAH Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 5 8 15 88 mm ...

Страница 41: ... 02 05 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH MODEL AOGA25FBTAH Sub accumulator Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 5 8 15 88 mm ...

Страница 42: ... 02 06 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH WIRING DIAGRAMS 444 MODEL AOSA18FBTAH ...

Страница 43: ... 02 07 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH MODEL AOGA25FBTAH ...

Страница 44: ...on pipe 2 Indoor unit is lower than outdoor unit H Indoor unit Outdoor unit Connection pipe 1 Indoor unit is higher than outdoor unit H Height difference H COOLING Pipe length m 5 7 5 10 15 20 Height difference H m 1 Indoor unit is higher than outdoor unit 8 0 983 0 979 0 977 5 0 997 0 992 0 988 0 984 0 982 0 1 005 1 000 0 996 0 992 0 990 2 Indoor unit is lower than outdoor unit 5 1 005 1 000 0 99...

Страница 45: ...s higher than outdoor unit H Height difference H COOLING Pipe length m 5 7 5 10 15 20 25 Height difference H m 1 Indoor unit is higher than outdoor unit 15 0 972 0 970 0 968 10 0 979 0 975 0 973 0 971 7 5 0 987 0 983 0 979 0 977 0 975 5 0 997 0 992 0 988 0 984 0 982 0 980 0 1 005 1 000 0 996 0 992 0 990 0 988 2 Indoor unit is lower than outdoor unit 5 1 005 1 000 0 996 0 992 0 990 0 988 7 5 1 000 ...

Страница 46: ...ant Charge z z MODEL AOGA25FBTAH Refrigerant Charge z z Refrigerant type R410A Refrigerant amount g 1 500 Total pipe length m 7 5 or less 15 20 Max 20 g m Additional charge g 0 150 250 Refrigerant type R410A Refrigerant amount g 1 800 Total pipe length m 7 5 or less 10 15 20 25 Max 20g m Additional charge g 0 50 150 250 350 ...

Страница 47: ... 02 11 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH AIRFLOW 777 MODEL AOGA18FBTAH MODEL AOGA25FBTAH Airflow m3 h 3 200 l s 889 CFM 1 884 Airflow m3 h 3 300 l s 917 CFM 1 942 ...

Страница 48: ...ctave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 MODEL AOGA25FBTAH Cooling z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 ...

Страница 49: ... 02 13 OUTDOOR UNIT AOGA18 25FBTAH OUTDOOR UNIT AOGA18 25FBTAH SOUND LEVEL CHECK POINT 88888 ...

Страница 50: ...echnical Standards and Codes Committee E0005 3 Limit voltage drop to less than 2 Increase conductor size if voltage drop is 2 or more Model name AOGA18FBTAH AOGA25FBTAH Power supply Voltage V 220 240 Frequency Hz 50 Max operating current 1 A 13 5 16 7 Starting current A 42 55 Wiring spec 2 Circuit breaker current A 20 30 Power cable mm2 2 5 3 0 2 5 3 5 Connection cable 3 mm2 1 5 2 5 Limited wiring...

Страница 51: ...FETY DEVICES 1111 Protection form Models AOGA18FBTAH AOGA25FBTAH Fan motor protection Thermal protection OFF 150 5 C ON 96 15 C High pressure protection Pressure switch OFF 4 9 0 1 MPa ON 3 8 0 15 MPa Compressor protection Over Load Protector OFF 160 165 C ON 90 10 C ...

Страница 52: ...DESIGN TECHNICAL MANUAL AIR CONDITIONER Duct type INDOOR ARGA30FMTA ARGA36FMTA ARGA45FMTA ARGA60FHTA OUTDOOR AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS DR_AR003EG_04 2015 10 02 ...

Страница 53: ...roduct specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer Copyright 2015 Fujitsu General Limited All rights reserved ...

Страница 54: ...7 5 1 Model ARGA30FMTA 17 5 2 Models ARGA36FMTA and ARGA45FMTA 18 5 3 Model ARGA60FHTA 19 6 Capacity table 20 6 1 Cooling capacity 20 7 Fan performance 22 7 1 Fan performance curve 22 8 Operation noise sound pressure 30 8 1 Noise level curve 30 8 2 Sound level check point 32 9 Safety devices 33 10 External input and output 34 10 1 Control input Operation Stop or Forced stop 34 10 2 External output...

Страница 55: ...36FRTAS AOGA45FRTAS and AOGA60FRTAS 64 5 Capacity compensation rate for pipe length and height difference 65 5 1 Model AOGA30FBTAS 65 5 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60FRTAS 66 6 Additional charge calculation 67 6 1 Model AOGA30FBTAS 67 6 2 Models AOGA36FRTAS and AOGA45FRTAS 67 6 3 Model AOGA60FRTAS 67 7 Airflow 68 7 1 Model AOGA30FBTAS 68 7 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60FR...

Страница 56: ...Part 1 INDOOR UNIT DUCT TYPE ARGA30FMTA ARGA36FMTA ARGA45FMTA ARGA60FHTA ...

Страница 57: ...alize a comfortable space 1 1 Model lineup 1 2 Features High efficiency technology ARGA30FMTA AOGA30FBTAS ARGA36FMTA ARGA45FMTA ARGA60FHTA AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS DC fan motor V Shape Heat exchanger High efficient Large diameter sirocco fan Optimized casing design Optimization of airflow speed distribution ...

Страница 58: ...all ability long piping correspondence AR36 45 60 Separated indoor unit AR60 only The indoor unit can be moved into the ceiling space through the designated opening Top class BTU 2 000 2 500 36 000 1 600 30 000 45 000 3 350 Hi h 60 000 35dB A cooling operation At rated point 30 model 50 m 20 m Ceiling Inspection hole Integration in the ceiling Separation ...

Страница 59: ...roller and the optional remote sensor allows flexibility in sensor location and suitable for all requirements Various timer setup available on off and weekly Equipped with weekly timer as standard function Start stop function is twice per day for a week When setting up the timer operation mode and tempera ture setup can be changed When a failure occurs the error code is displayed Error history Las...

Страница 60: ... week Possible to set temperature for two time spans and for each day of the week At Weekly timer Set back timer setup 1 remote controller A Remote controller cable A 500 m SU MO TU WE TH FR SA 7 3 12 6 9 15 18 21 SU MO TU WE TH FR SA 7 3 12 6 9 15 18 21 Easy to understand time bar display Setup screen example Set to Wednesday 8 00 to 20 00 Screen after setup 24 C 0 3 6 9 12 15 18 21 Time SU MO TU...

Страница 61: ...j TIMER DELETE button Deletes the weekly timer schedule k TIMER SET button Sets the date hour minute and on off time l Vertical airflow direction and swing button Push for 2 seconds to change the swing mode m Horizontal airflow direction and swing button Push for 2 seconds to change the swing mode n FILTER RESET button o Operation lamp Lights during operation and when the timer is on p Timer and c...

Страница 62: ...ed remote controller are as follows 2 4 Wring specifications Unit mm Size H W D mm 120 120 18 Weight g 160 Cable length accessory m 10 Power V 12 Use Cable size Wire type Remarks Remote controller cable 0 33 mm2 22 AWG Polar 3 core Use sheathed PVC cable 120 120 120 18 Side View Front View ...

Страница 63: ...W D Net mm 300 1000 700 Gross 400 1238 875 Weight Net kg 35 Gross 43 Connection pipe Size Liquid mm in Ø 9 52 Ø 3 8 Gas Ø 15 88 Ø 5 8 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Remote controller type Wired Drain hose Material PVC Size mm Ø 25 I D Ø 32 O D NOTES Specifications are based on the following conditions Cooling T1 Indoor temperature of 27 CDB 19 CWB and outdoor tempera...

Страница 64: ...8 39 9 546 1158 39 9 Fin pitch 1 4 1 3 Rows Stages 3 20 3 26 Pipe type Copper Fin type Aluminum Enclosure Material Steel Color Dimensions H W D Net mm 300 1400 700 360 1400 850 Gross 400 1638 875 460 1640 1030 Weight Net kg 44 67 Gross 53 77 Connection pipe Size Liquid mm in Ø 9 52 Ø 3 8 Gas Ø 19 05 Ø 3 4 Method Flare Operation range Cooling C 18 to 32 RH 80 or less Remote controller type Wired Dr...

Страница 65: ... 10 DUCT TYPE ARGA30 60F 4 Dimensions 4 1 Model ARGA30FMTA Unit mm Air Gas pipe Drain port Control box Liquid pipe Side view L Side view R Top view Front view Rear view ...

Страница 66: ... 11 DUCT TYPE ARGA30 60F 4 2 Models ARGA36FMTA and ARGA45FMTA Unit mm Gas pipe Drain port Control box Liquid pipe Air Side view L Side view R Top view Front view Rear view ...

Страница 67: ... 12 DUCT TYPE ARGA30 60F 4 3 Model ARGA60FHTA Unit mm Gas pipe Drain port Control box Liquid pipe Air Side view R Top view Side view L Front view Rear view ...

Страница 68: ... by which service space is made on top of the unit recommended Installation by which service is carried out from the bottom of the unit Floor 300 or more 150 or more 20 or more 2500 or more When no ceiling 20 or more Unit mm Unit mm 450 or more 500 or more 150 or more 20 or more 2500 or more When no ceiling Unit mm 500 or more 150 or more 20 or more 20 or more 2500 or more When no ceiling ...

Страница 69: ...mination in the maintenance space as they will impede service Model ARGA30FMTA Provide a service access for maintenance purposes The service access necessary for fan units and filter maintenance Bottom view AIR Unit mm Control box 300 or more 500 or more 500 or more Service access AIR Service access Fan unit side 300 or more 500 or more 1400 or more 100 Bottom view Unit mm ...

Страница 70: ...access for maintenance purposes The service access necessary for fan units and filter maintenance 300 or more 500 or more Service access 500 or more Control box AIR Bottom view Unit mm AIR 300 or more Service access 1800 or more 100 500 or more Fan unit side Bottom view Unit mm ...

Страница 71: ... DUCT TYPE ARGA30 60F Model ARGA60FHTA AIR Service access 700 or more 700 or more 500 or more Control box Bottom view Unit mm Bottom view Service access 2000 or more 100 500 or more 500 or more AIR Unit mm ...

Страница 72: ... 17 DUCT TYPE ARGA30 60F 5 Wiring diagrams 5 1 Model ARGA30FMTA ...

Страница 73: ... 18 DUCT TYPE ARGA30 60F 5 2 Models ARGA36FMTA and ARGA45FMTA ...

Страница 74: ... 19 DUCT TYPE ARGA30 60F 5 3 Model ARGA60FHTA ...

Страница 75: ... 2 84 25 10 72 8 72 2 43 10 99 8 76 2 46 11 23 8 81 2 48 11 65 9 30 2 52 11 83 9 26 2 53 12 15 9 17 2 57 12 44 9 55 2 59 30 10 03 8 31 2 66 10 32 8 37 2 69 10 56 8 47 2 72 10 96 8 96 2 76 11 13 8 94 2 77 11 45 8 85 2 81 11 76 9 26 2 84 35 9 34 7 97 2 91 9 52 8 03 2 92 9 76 8 08 2 95 10 12 8 57 2 99 10 30 8 54 3 01 10 63 8 49 3 05 10 95 8 93 3 09 40 8 36 6 02 3 08 8 73 6 73 3 16 9 00 7 36 3 22 9 53...

Страница 76: ... 14 90 10 98 4 01 15 28 11 96 4 05 16 02 12 99 4 12 16 31 13 25 4 16 16 98 13 65 4 19 18 16 13 75 4 28 35 13 90 8 81 4 22 13 90 10 66 4 31 14 38 11 44 4 35 15 13 12 46 4 43 15 20 12 92 4 47 16 25 13 06 4 50 17 35 13 54 4 60 40 12 35 9 11 4 58 12 89 10 17 4 69 13 28 11 14 4 78 14 07 12 15 4 88 14 41 12 44 4 89 15 01 12 99 4 96 16 17 13 18 5 00 46 11 51 8 93 5 06 12 07 10 04 5 20 12 47 10 78 5 30 13...

Страница 77: ...389 414 364 383 344 356 319 CFM 988 824 876 771 812 729 753 676 LOW Static pressure Pa 16 38 42 53 59 67 72 81 Airflow m3 h 1540 1280 1360 1210 1270 1130 1170 1050 l s 428 356 378 336 353 314 325 292 CFM 906 753 800 712 747 665 688 618 QUIET Static pressure Pa 10 29 34 42 44 52 56 64 Airflow m3 h 1370 1120 1210 1100 1110 980 1020 920 l s 381 311 336 306 308 272 283 256 CFM 806 659 712 647 653 576 ...

Страница 78: ...ult setting is set at Normal mode Characteristics of air volume and capacity Cooling Fan performance curve_2 For function setting by remote controller 1800 900 0 140 130 120 110 100 90 80 70 60 50 40 30 20 10 1000 1100 1200 1300 1400 1500 1600 1700 1900 Airflow m3 h External Static Pressure Pa Hi High static pressure 3 120Pa Hi High static pressure 2 90Pa Hi Normal 30Pa Hi High static pressure 1 6...

Страница 79: ...53 439 CFM 1129 1006 1088 971 1065 900 959 929 LOW Static pressure Pa 24 35 38 47 63 74 83 86 Airflow m3 h 1790 1610 1650 1440 1670 1420 1490 1450 l s 497 447 458 400 464 394 414 403 CFM 1053 947 971 847 982 835 876 853 QUIET Static pressure Pa 19 28 32 39 50 60 60 63 Airflow m3 h 1610 1440 1510 1310 1490 1280 1280 1230 l s 447 400 419 364 414 356 356 342 CFM 947 847 888 771 876 753 753 724 2100 1...

Страница 80: ...e default setting is set at Normal mode Characteristics of air volume and capacity Cooling 2100 1200 0 140 130 120 110 100 90 80 70 60 50 40 30 20 10 1300 1400 1500 1600 1700 1800 1900 2000 Airflow m3 h External Static Pressure Pa Fan performance curve_2 For function setting by remote controller Hi High static pressure 1 90Pa Hi Normal 60Pa Hi High static pressure 2 120Pa Hi Low static pressure 30...

Страница 81: ... 1212 1400 1212 1294 1124 1124 1076 LOW Static pressure Pa 23 33 44 58 65 78 78 83 Airflow m3 h 2160 1910 2190 1900 2020 1740 1740 1670 l s 600 531 608 528 561 483 483 464 CFM 1271 1124 1288 1118 1188 1024 1024 982 QUIET Static pressure Pa 18 28 36 48 48 58 62 66 Airflow m3 h 2000 1760 2000 1730 1730 1500 1550 1490 l s 556 489 556 481 481 417 431 414 CFM 1176 1035 1176 1018 1018 882 912 876 2600 1...

Страница 82: ... is set at Normal mode Characteristics of air volume and capacity Cooling 2600 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Airflow m3 h 0 140 130 120 110 100 90 80 70 60 50 40 30 20 10 External Static Pressure Pa Fan performance curve_2 For function setting by remote controller Hi High static pressure 2 120Pa Hi High static pressure 1 90Pa Hi Normal 60Pa Hi Low static pressure 30Pa...

Страница 83: ... 708 675 CFM 1865 1588 1659 1518 1600 1488 1500 1429 LOW Static pressure Pa 45 70 67 86 97 110 115 123 Airflow m3 h 2950 2550 2580 2370 2520 2370 2410 2300 l s 819 708 717 658 700 658 669 639 CFM 1735 1500 1518 1394 1482 1394 1418 1353 QUIET Static pressure Pa 37 55 57 67 85 96 95 101 Airflow m3 h 2650 2270 2370 2130 2340 2210 2190 2100 l s 736 631 658 592 650 614 608 583 CFM 1559 1335 1394 1253 1...

Страница 84: ...ve_2 above The default setting is set at Normal mode Characteristics of air volume and capacity Cooling Fan performance curve_2 For function setting of remote controller 2000 2200 2400 2600 2800 3000 3200 3400 External Static Pressure Pa 0 20 40 60 80 100 120 140 160 180 200 Hi Normal 60Pa Airflow m3 h Hi High static pressure 2 130Pa Hi High static pressure 1 100Pa Hi High static pressure 3 160Pa ...

Страница 85: ...C 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET ...

Страница 86: ... sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 HIGH QUIET ...

Страница 87: ...UCT TYPE ARGA30 60F 8 2 Sound level check point Center Front view Microphone Center Side view Product Air 1 5 m 2 m 1 m Microphone Measuring duct Set the static pressure as rating in this area Measuring duct ...

Страница 88: ...otection form Model ARGA30FMTA ARGA36FMTA ARGA45FMTA ARGA60FHTA Circuit protection Current fuse PCB 250 V 5 A Fan motor protection Thermal protection program Activate 115 15 C Fan motor stop Reset 70 C Fan motor restart Current protection Activate 7 9 A Fan motor stop ...

Страница 89: ...tting is in Operation Stop mode Connector Input Output Remarks CN102 Control input See external input output settings for details CN103 Operation status output CN6 Fresh air control output Connector Input Output Remarks CN46 Control input See external input output settings for details CN47 Operation status output Error status output Fresh air control output Unit operation Initial setting after pow...

Страница 90: ...ptional part Model name Exterior UTD ECS5A External input wire Remote controller On On On Input signal On Off Indoor unit Operation Stop Remote controller On On On Input signal Indoor unit Command Remote control operation invalidity On Off Operation Stop Forced stop Normal ...

Страница 91: ...tus output Circuit diagram example Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA Optional part Model name Exterior UTD ECS5A External output wire For 30 36 45 models For 60 model Locally purchased Example Display Indoor unit control PCB Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V On Off...

Страница 92: ...l becomes off Circuit diagram example Make the distance from the PCB to the connected unit within 10 m Relay spec Rated DC 12 V 50 mA or less Model name Exterior UTD ECS5A External output wire Locally purchased Example Display Indoor unit control PCB Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V On Off Operation Stop Indoor unit Output signal Locally purc...

Страница 93: ... 38 DUCT TYPE ARGA30 60F Optional part Model name Exterior UTD ECS5A Fresh air output wire On Off Operation Stop Indoor unit Output signal ...

Страница 94: ...function settings Models ARGA30FMTA ARGA36FMTA and ARGA45FMTA By using some components on the PCB you can change the function settings Related components on the PCB and the applicable settings Component location Components on the indoor unit main PCB used for the function settings are located as shown in the following figure Component Setting content DIP switch 1 Remote controller address setting ...

Страница 95: ...etting JM1 Setting change prohibited JM2 Setting change prohibited JM3 Setting change prohibited Remote controller address DIP switch number Factory setting 1 2 3 4 00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ...

Страница 96: ...n operating a number of indoor units by using a wired remote controller DIP switch setting for assigning unit number to each indoor unit is required DIP switches are normally set to make the unit number 00 Remote controller address DIP switch number Factory setting 1 2 3 4 00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07...

Страница 97: ...UCT TYPE ARGA30 60F Switch 1 Setting change prohibited SW101 Switch 2 Setting change prohibited SW101 Switch 3 Setting change prohibited SW101 00 01 02 Remote controller address Indoor unit Remote controller ...

Страница 98: ...d vacuuming have been performed firmly There is no wiring mistake 1 Turn on the power 2 Press the SET TEMP buttons and FAN button simultaneously for more than 5 seconds to enter the function setting mode 3 Press the SET BACK button to select the indoor unit number when you set the remote controller address setting 4 Press the set time buttons to select the function number 5 Press the SET TEMP butt...

Страница 99: ...ng mode In addition the function setting mode will be automatically canceled after 1 minute if no oper ation is performed 8 After completing the function setting be sure to turn off the power and turn it on again CAUTION After turning off the power wait 30 seconds or more before turning on the power again The function setting will not become active unless the power is turned off then on again ...

Страница 100: ...cooling 4 40 Auto restart 5 42 Room temperature sensor switching 6 46 External input control 7 48 Room temperature sensor switching Aux 8 60 Switching functions for external output terminal Function number Setting value Setting description Factory setting 11 00 Standard 2 500 hours 01 Long interval 4 400 hours 02 Short interval 1 250 hours 03 No indication Function number Setting value Setting des...

Страница 101: ...ntroller are active NOTE Remote controller sensor must be turned on by using the remote controller 6 External input control Operation Stop mode or Forced stop mode can be selected 7 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to Wired remote controller 01 This function will only work if the function setting 42 is set at...

Страница 102: ...rminal Functions of the external output terminal can be switched For details refer to External input and output Only for 60 model Function number Setting value Setting description Factory setting 60 00 Operation status 09 Error status 10 Indoor unit fan operation status ...

Страница 103: ...n settings for the remote controller Switches are fixed at OFF initially SW6 Memory backup setting Set to ON to use the batteries for memory backup If the batteries are not used all of the settings stored in the memory will be deleted if there is power failure NOTE In case of simple remote controller do not turn it on DIP switch 1 SW1 Setting change prohibited SW2 Setting change prohibited SW3 Set...

Страница 104: ...can be offered by installing Remote sensor unit in the remote controller Long life filter UTD LFNB Long life filter can be mounted to the indoor unit For 30 model Long life filter UTD LFNA Long life filter can be mounted to the indoor unit For 36 and 45 models Long life filter UTD LFKA Long life filter can be mounted to the indoor unit For 60 model Drain pump unit UTZ PX1NAA Optional drain lift up...

Страница 105: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS ...

Страница 106: ... Amount cm3 858 Enclosure Material Steel Color Beige Approximate color of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 914 970 370 Gross 1048 1064 479 Weight Net kg 77 Gross 85 Connection pipe Size Liquid mm in Ø 9 52 Ø 3 8 Gas Ø 15 88 Ø 5 8 Method Flare Pre charge length m 7 5 Max length 30 Max height difference 15 Operation range Cooling C 21 to 52 NOTES Specifications are based on the following ...

Страница 107: ...ype POE Amount cm3 1242 Enclosure Material Steel Color Beige Approximate color of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 1290 900 330 Gross 1430 1050 445 Weight Net kg 100 102 107 Gross 108 110 115 Connection pipe Size Liquid mm in Ø 9 52 Ø 3 8 Gas Ø 19 05 Ø 3 4 Method Flare Pre charge length m 20 Max length 50 Max height difference 30 Operation range Cooling C 21 to 52 NOTES Specifications a...

Страница 108: ...le port 65 15 50 14 166 370 24 40 410 50 Gas 42 Liquid 650 154 36 8 24 370 50 227 341 305 438 622 4 87 89 970 914 21 8 399 25 131 409 745 50 95 Ø2 8 Ca ble po rt Ø28 Unit mm Top view Front view Side view Rear view Bottom view Detail A Terminal blocks 2 way valve Liquid 3 way valve Gas Pipe port Liquid valve Gas valve Pipe port Pipe port Pipe cable port ...

Страница 109: ...T AOGA30 60F 2 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS Unit mm 900 1290 77 31 21 370 9 400 650 151 99 196 170 4 Ø12mm hole 12 330 Air flow Drain cap mounting places Top view Side view Bottom view Front view ...

Страница 110: ... there are obstacles at the rear only When there are obstacles at the rear and sides When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 150 or more 200 or more 300 or more 200 or more 1 000 or more 150 or more 1 000 or more 300 or more Max 500 1 000 or ...

Страница 111: ...Unit mm When there are obstacles at the rear only When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above 300 or more 250 or more 1 500 or more 250 or more 500 or more 1 500 or more 250 or more 1 500 or more 500 or more 250 or more Max 300 1 500 or more ...

Страница 112: ...floor level should be 50 mm or more When installing the outdoor unit be sure to open the front and left side to obtain better operation efficiency Unit mm Single parallel unit arrangement Multiple parallel unit arrangement 500 or more 600 or more 1 500 or more 3 000 or more 500 or more 600 or more 1 500 or more 250 or more 3 500 or more 250 or more 150 1 500 or more 500 or more 250 or more ...

Страница 113: ... only When there are obstacles at the rear and sides When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 150 or more 200 or more 200 or more 300 or more 1000 or more 1000 or more 150 or more 300 or more Max 500 1 000 or more Max 5 000 500 or more 250 or ...

Страница 114: ...tion in the upper space Unit mm When there are obstacles at the rear only When there are obstacles at the front only When there are obstacles at the front and rear Unit mm When there are obstacles at the rear and above 300 or more 1 500 or more 500 or more 1 500 or more 1 500 or more 1 500 or more 500 or more Max 300 ...

Страница 115: ... Height above the floor level should be 50 mm or more When installing the outdoor unit be sure to open the front and left side to obtain better operation efficiency Unit mm Single parallel unit arrangement Multiple parallel unit arrangement 1 000 or more 2 000 or more 600 or more 150 or more 3 000 or more 600 or more 1 500 or more 500 or more 150 500 or more 1 500 or more ...

Страница 116: ... 61 OUTDOOR UNIT AOGA30 60F 3 Refrigerant circuit 3 1 Model AOGA30FBTAS Sub accumulator High pressure switch ...

Страница 117: ... 62 OUTDOOR UNIT AOGA30 60F 3 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...

Страница 118: ... 63 OUTDOOR UNIT AOGA30 60F 4 Wiring diagrams 4 1 Model AOGA30FBTAS ...

Страница 119: ... 64 OUTDOOR UNIT AOGA30 60F 4 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS ...

Страница 120: ... 0 988 0 979 0 963 10 0 996 0 988 0 979 0 963 7 5 1 000 0 996 0 988 0 979 0 963 5 1 027 1 000 0 996 0 988 0 979 0 963 0 1 027 1 000 0 996 0 988 0 979 0 963 Indoor unit is lower than outdoor unit 2 5 1 018 0 992 0 988 0 980 0 972 0 955 7 5 0 988 0 984 0 976 0 968 0 951 10 0 980 0 972 0 965 0 948 15 0 964 0 956 0 940 Height difference H Indoor unit is higher than outdoor unit 1 Indoor unit is lower ...

Страница 121: ...25 0 893 0 867 0 840 20 0 919 0 893 0 867 0 840 15 0 919 0 893 0 867 0 840 10 0 985 0 919 0 893 0 867 0 840 7 5 1 000 0 985 0 919 0 893 0 867 0 840 5 1 014 1 000 0 985 0 919 0 893 0 867 0 840 0 1 014 1 000 0 985 0 919 0 893 0 867 0 840 Indoor unit is lower than outdoor unit 2 5 1 005 0 992 0 977 0 912 0 886 0 860 0 834 7 5 0 988 0 973 0 908 0 882 0 856 0 830 10 0 969 0 905 0 879 0 853 0 827 15 0 8...

Страница 122: ... R410A Factory charge amount g 2500 Total pipe length m 7 5 or less 10 20 30 Max 20 g m Additional charge amount g 0 50 250 450 Refrigerant type R410A Factory charge amount g 3400 Total pipe length m 20 or less 30 40 50 Max 40 g m Additional charge amount g 0 400 800 1200 Refrigerant type R410A Factory charge amount g 4300 Total pipe length m 20 or less 30 40 50 Max 40 g m Additional charge amount...

Страница 123: ...IT AOGA30 60F 7 Airflow 7 1 Model AOGA30FBTAS Cooling 7 2 Models AOGA36FRTAS AOGA45FRTAS and AOGA60 FRTAS Cooling Airflow m3 h 4400 4400 l s 1222 1222 CFM 2590 2590 Airflow m3 h 5700 6100 l s 1583 1695 CFM 3355 3590 ...

Страница 124: ... µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 ...

Страница 125: ...nd sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 ...

Страница 126: ...nt NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above 1 m Center Microphone Microphone Rear Center Airflow Rear view Side view 1 m Airflow Center Microphone Microphone Rear Rear view Side view Center ...

Страница 127: ...te devices complied to the regional standard 3 Limit voltage drop to less than 2 If voltage drop is 2 or more increase cable conductor size Model name AOGA30FBTAS AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS Power supply Voltage V 220 240 3N 380 415 Frequency Hz 50 Max operating current 1 A 23 0 10 5 14 0 15 5 Starting current A 60 43 47 67 Wiring spec 2 Circuit breaker current A 30 20 Earth leakage breake...

Страница 128: ...m Model AOGA36FRTAS AOGA45FRTAS AOGA60FRTAS Circuit protection Current fuse Near the terminal 250 V 5 A 250 V 10 A Current fuse Main PC board 250 V 6 3 A Fan motor protection Thermal protection program Activate 150 5 C Fan motor stop Reset 96 15 C Fan motor restart High pressure protection High pressure switch Activate 4 9 MPa Compressor stop Reset 3 8 MPa Compressor restart Compressor protection ...