Operation example
Breakdown of electricity charges in general and the corresponding operation of the system for each
item is as follows.
Reduced by indoor unit
rotation control
Control target value:
Indoor unit stoppage rate (%)
Operation status is checked
by power consumption graph
display.
Reduced by outdoor unit
capacity save control
Control target value:
Outdoor unit capacity upper
limit rate (%)
Reduced by peak cut control
Control target value:
Target average power (kW)
Electric charge (power consumption) = Basic Usage Demand charge
Basic charge
Charge billed according to contract with the electric power company. Includes meter
reading cost and billing cost.
Usage charge
Charge billed according the power consumed.
Demand charge
Charge billed according to the scale of the contract with the electric power company.
¢
Notes on energy saving function
Energy saving function precautions and scope of guarantee:
The effect of the energy saving function depends on the units used in the system, usage environ-
ment, installation environment, and so forth. Each energy saving function is not guaranteed to dis-
play a fixed effect and function for operation by specific setting. Before using the function, read and
understand the following precautions.
•
How to use the energy saving function:
Since the effect of the energy saving function depends on the units used in the system, usage en-
vironment, installation environment, and so forth, a different effect may appear according to the
building and operating period even when operated with the same settings and schedule. Try to
gain an understanding of the features of each energy saving function and confirm the actual effect
through operation and apply appropriate settings, etc. as required.
•
Target electric power of peak cut function:
These are values used as target values when performing peak cut control. These values do not
always guarantee that the consumed power is within the target value. For example, even if forced
thermostat off and outdoor unit stoppage are activated, the control become ineffective if the out-
door unit is performing a protective operation (oil recovery and defrosting). As a result, the electric
power consumed may exceed the target electric power.
•
Relationship between unit protection and energy saving function:
For VRF, there are operations and restrictions for protecting units. The energy saving function op-
erates within the range of these protective operations and restrictions. When the energy saving
function performs control against these protective operations and restrictions, the protective opera-
tions and restrictions have priority and the energy saving function is either restricted or may not
operate. As protective operations of units, there are oil recovery, defrosting, etc. which are auto-
matically performed periodically or under specified conditions.
2-25. Energy saving setting on System controller
- (07-135) -
2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Содержание AIRSTAGE J-IIIL
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Страница 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Страница 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Страница 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Страница 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Страница 113: ...6 2 Model AOU120RLAVL 6 2 Model AOU120RLAVL 03 17 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...
Страница 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Страница 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Страница 194: ...5 4 Mini duct type Model ARUL4TLAV1 5 4 Mini duct type 04 70 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 203: ... Models ASUA12TLAV1 and ASUA14TLAV1 5 11 Wall mounted type 04 79 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 205: ... Models ASUA30TLAV2 and ASUA36TLAV2 5 11 Wall mounted type 04 81 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 206: ... Models ASUA7TLAV and ASUA12TLAV 5 11 Wall mounted type 04 82 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...
Страница 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Страница 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Страница 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Страница 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Страница 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Страница 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Страница 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...