1-1-1. EXTERNAL INPUT
Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation
peak control setting, emergency/batch stop and electricity meter pulse are possible from The
electricity meter connections that are can be used by the System Controller are shown below.
WIRING METHOD AND SPECIFICATIONS
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft. (150 m)
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed
*For each input, pin No.1 is of positive polarity and pin No.2 is the ground.
1 2
1 2
1 2
1 2
1 2
CN131
(Yellow)
Input1
connected unit connected unit connected unit connected unit connected unit
Input2
Input3
Input4
Input5
CN132
(Green)
CN133
(White)
CN134
(Red)
CN135
(Orange)
P.C.B
OPERATION BEHAVIOR
Connector
Input signal
Status
Outdoor unit
Master
Slave
CN131 (Yellow)
OFF
Normal operation
○
ON
Low noise mode operation
CN132 (Green)
*1
OFF
Cooling priority
○
ON
Heating priority
CN133 (White)
OFF
Normal operation
○
ON
Outdoor unit operation peak control
CN134 (Red)
OFF
Normal operation
○
ON
Batch stop or Emergency stop operation *2, *3
CN135 (Orange)
*4
No pulse
No information from electricity meter
○
○
Pulse
Power usage information from electricity meter
Slave unit can connect only input5 (CN135).
NOTES :
*1: The "external input priority mode" must be set by pressing push button on PCB of outdoor unit.
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PCB push button.
*3: The emergency stop function is not guaranteed to meet the regulations of each country.
Consult local codes regarding use. Especially, since the emergency-stop may not function in the
case of broken wiring to the external input terminals and communication line, communication
errors due to noise, VRF external input circuit troubles, etc. In such cases, backup measures
that add direct interruption of the power supply is recommended.
*4: Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or more.
- (08 - 03) -
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
Содержание Airstage AGUA12TLAV1
Страница 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Страница 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Страница 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Страница 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Страница 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Страница 194: ... INSTALLATION PLACE Unit in mm 1 25 3 70 5 122 8 200 3 62 4 80 60 1 500 71 1 800 04 61 INDOOR UNITS INDOOR UNITS ...
Страница 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Страница 204: ... MODELS AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV 04 71 INDOOR UNITS INDOOR UNITS ...
Страница 206: ...4 3 CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 04 73 INDOOR UNITS INDOOR UNITS ...
Страница 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Страница 209: ...4 6 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARUM24TLAV ARUM30TLAV ARUM36TLAV 04 76 INDOOR UNITS INDOOR UNITS ...
Страница 210: ...4 7 HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Страница 213: ...4 9 COMPACT FLOOR TYPE MODELS AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 04 80 INDOOR UNITS INDOOR UNITS ...
Страница 214: ...4 10 FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 04 81 INDOOR UNITS INDOOR UNITS ...
Страница 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Страница 216: ...4 12 WALL MOUNTED TYPE MODELS ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 04 83 INDOOR UNITS INDOOR UNITS ...
Страница 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Страница 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Страница 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Страница 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Страница 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Страница 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Страница 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Страница 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Страница 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Страница 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Страница 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Страница 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...