![Fujitsu AGYG09KVCA Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/fujitsu/agyg09kvca/agyg09kvca_design-and-technical-manual_118124128.webp)
¢
Combination of external input and output
By combining the function setting of the indoor unit, you can select various combinations of func-
tions.
Combination examples of external input and output are as follows:
Mode
Function
setting
External input
Indoor unit
CN14
CN15
0
60-00
Operation/Stop (Function setting 46-00)
or
Forced stop (Function setting 46-02)
Forced thermostat Off
9
60-09
Forced thermostat Off
10
60-10
Forced thermostat Off
11
60-11
Forced thermostat Off
12
60-12
Forced thermostat Off
Mode
Function
setting
External output
Indoor unit
CN20
CN21
CN22
CN23
0
60-00
Operation/Stop
Error status
Indoor unit fan
operation status
External heater
output
9
60-09
Error status
Operation/Stop
Indoor unit fan
operation status
External heater
output
10
60-10
Indoor unit fan
operation status
Operation/Stop
Error status
External heater
output
11
60-11
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
NOTE:
Input of Operation/Stop depends on the settingof function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01:(Setting prohibited)
02: Forced stop
03: Operation/Stopmode 2 (R.C. disabled)
Input signal type
•
Indoor unit
Input signal type is only "Edge".
Edge
- 122 -
11-4. Floor type
11. External input and output
2-UNIT
MULTI-SPLIT TYPE
2-UNIT